Main Circuit Wiring

WARNING!

Electrical Shock Hazard. Do not connect the AC power line to the drive output terminals U/T1, V/T2, and W/T3 . Failure to

comply could result in death or serious injury by fire as a result of drive damage from line voltage application to output terminals.

NOTICE

Refer to the P1000 Technical Manual SIEPYAIP1U01 on the CD-ROM packaged with the product for complete product
instructions necessary for proper installation, set-up, troubleshooting and maintenance. CD part number TOECC71061615.

NOTICE:

Route motor leads U/T1, V/T2, and W/T3 separate from all other leads to reduce possible interference related issues. Failure to

comply may result in abnormal operation of drive and nearby equipment.
NOTICE:

Do not use the negative DC bus terminal “–” as a ground terminal. This terminal is at high DC voltage potential. Improper wiring

connections could damage the drive.
NOTICE:

Do not solder the ends of wire connections to the drive. Soldered wiring connections can loosen over time. Improper wiring practices

could result in drive malfunction due to loose terminal connections.
NOTICE:

Do not switch the drive input to start or stop the motor. Frequently switching the drive on and off shortens the life of the DC bus

charge circuit and the DC bus capacitors, and can cause premature drive failures. For the full performance life, refrain from switching the

drive on and off more than once every 30 minutes.
NOTICE:

When connecting the motor to the drive output terminals U/T1, V/T2, and W/T3, the phase order for the drive and motor should

match. Failure to comply with proper wiring practices may cause the motor to run in reverse if the phase order is backward.
NOTICE:

Do not connect phase-advancing capacitors or LC/RC noise filters to the output circuits. Failure to comply could result in damage

to the drive, phase-advancing capacitors, LC/RC noise filters or ground fault circuit interrupters.

Note:

Wire gauge recommendations based on drive continuous current ratings (ND) using 75 °C 600 Vac vinyl-sheathed wire assuming ambient

temperature within 40 °C and wiring distance less than 100 m.

Yaskawa recommends using closed-loop crimp terminals on all drive models. To maintain UL/cUL approval, UL Listed

closed-loop crimp terminals are specifically required when wiring the drive main circuit terminals on models 2A0110 to

2A0415, 4A0058 to 4A1200, and 5A0041 to 5A0242. Use only the tools recommended by the terminal manufacturer for

crimping.

u

Main Circuit Terminal Functions

Table i.3 Main Circuit Terminal Functions

Terminal

Type

Function

Page

200 V

Class

Drive Model

2A0004 to

2A0081

2A0110, 2A0138

2A0169 to

2A0415

400 V

Class

4A0002 to

4A0044

4A0058, 4A0072

4A0088 to

4A0675

4A0930, 4A1200

600 V

Class

5A0003 to

5A0032

5A0041, 5A0052

5A0062 to

5A0242

R/L1

Main circuit power supply input

Connects line power to the drive

19

S/L2

T/L3

R1-L11

Not available

Main circuit power

supply input

Connects line power to the drive

Remove the shorting bars

connecting R/L1-R1/L11, S/L2-

S1/L21, T/L3-T1/L31 when

using 12-phase rectification.

S1-L21

T1-L31

U/T1

Drive output

Connects to the motor

19

V/T2

W/T3

B1

Braking resistor

Not available

Available for connecting a

braking resistor or a braking

resistor unit option

B2

i.3 Electrical Installation Safety

YASKAWA ELECTRIC TOEP YAIP1U 03B YASKAWA AC Drive – P1000 Safety Precautions

21