I.3 electrical installation safety – Yaskawa CIMR-PU User Manual
Page 30

Drive Model
Terminal
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw
Size
Tightening Torque
N·m (lb.in.)
5A0062
R/L1, S/L2, T/L3
4
10 to 4/0
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
4
10 to 4/0
⊖, ⊕1
–
4 to 4/0
⊕3
–
6 to 4/0
4
4
5A0077
R/L1, S/L2, T/L3
3
10 to 4/0
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
3
10 to 4/0
⊖, ⊕1
–
3 to 4/0
⊕3
–
6 to 4/0
4
4
5A0099
R/L1, S/L2, T/L3
1/0
10 to 4/0
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
1
10 to 4/0
⊖, ⊕1
–
2 to 4/0
⊕3
–
4 to 4/0
4
4
5A0125
R/L1, S/L2, T/L3
2/0
1 to 300
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
2/0
1 to 300
⊖, ⊕1
–
2/0 to 3/0
⊕3
–
1 to 1/0
3
4 to 300
5A0145
R/L1, S/L2, T/L3
3/0
2/0 to 300
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
3/0
2/0 to 300
⊖, ⊕1
–
3/0 to 4/0
⊕3
–
1/0 to 2/0
3
4 to 300
5A0192
R/L1, S/L2, T/L3
300
2/0 to 600
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
250
2/0 to 600
⊖, ⊕1
–
2/0 to 400
⊕3
–
2/0 to 250
M10
18 to 23
(159 to 204)
1
1 to 350
M12
32 to 40
(283 to 354)
5A0242
R/L1, S/L2, T/L3
400
2/0 to 600
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
350
2/0 to 600
⊖, ⊕1
–
2/0 to 500
⊕3
–
250 to 300
M10
18 to 23
(159 to 204)
1
1 to 350
M12
32 to 40
(283 to 354)
Note:
When connecting peripheral devices or options to terminals
⊖, ⊕1, ⊕3, B1, and B2 , refer to the instruction manual for each device. For
more information, contact Yaskawa or your nearest sales representative.
i.3 Electrical Installation Safety
30
YASKAWA ELECTRIC TOEP YAIP1U 03B YASKAWA AC Drive – P1000 Safety Precautions