Note: The current input for terminal A1 is not available on the V1000-4X. Use terminal A2 for current input.
Network Communications Terminals
"–" indicates that an equivalent terminal on the other unit does not exist.
FR
A1
Analog input 1
Voltage or current (not available on V1000 -
see Note) input (frequency reference)
0~+10 VDC (20 kW),
0 or 4~20 mA (250 kW)
0~+10 VDC (20 kW)
—
A2
Analog input 2
(frequency reference)
—
DC:0~+10 V (20 k )
0 or 4~20 mA (250 k )
(initial setting: 4-20 mA)
FC
AC
Analog input common
0 V
—
HC
Hard wire baseblock common
—
+24 V (max. current 10 mA)
—
H1
Hard wire baseblock input
(EN954-1, category 3, Stop category 0)
—
Open: Stop
Closed: Operation
MA
Multi-Function Digital Output
(N.O. Contact) (Fault)
Max. AC load:
250 VDC, 1 A max.
30 VDC, 1 A max.
Max. load:
AC:250 V, 10 mA~1 A
DC:30 V, 10 mA~1 A
MB
Multi-Function Digital Output
(N.O. Contact) (Fault)
MC
Multi-Function Digital Output
(common)
P1
Open collector output 1
(during run)
Photocoupler +48 VDC, 50 mA or less Output
P2
Open collector output 2
(speed agree)
PC
Open collector output common
—
MP
Pulse output
(output frequency)
—
Max. 32 kHz
AM
Analog output
DC:0~+10 V, 2 mA max.
Resolution: 8 bit
DC:0~+10 V, 2 mA max.
Resolution: 1/1000
AC
Analog output GND
Serial
Communication
Terminals
Function
Signal Level
V74X
V1000-
4X
V74X
V1000-4X
R+
R+
Receive +
RS-485/422 MEMOBUS
Protocol
Max. 19.2 kbps
RS-485/422 MEMOBUS
Protocol
Max. 115.2 kbps
R-
R-
Receive -
S+
S+
Transmit +
S-
S-
Transmit -
GND
IG
Shield connection, GND
—
0V
Control
Terminals
Function
Signal Level
V74X
V1000-
4X
V74X
V1000-4X