Yaskawa VS606 V74X V7 to V1000 User Manual
Page 21

PL.V1000-4X.01 Transition Guide 6/22/10
Page 21 of 32
Yaskawa America, Inc.
Product Transition Guide
PL. V1000-4X.01 Rev: 6/22/10
Carrier frequency
selection
n080
4
C6-02
o2-04
dep.
V74X
V1000-4X
Carrier frequency upper
limit
C6-03
C6-02
dep.
n080 1
C6-02 1 (2kHz)
Carrier frequency lower
limit
C6-04
C6-02
dep.
n080 2
C6-02 2 (5kHz)
Carrier frequency
proportional gain
C6-05
0
n080 3
C6-02 3 (8kHz)
n080 4
C6-02 4 (10kHz)
n080 7~9
C6-03/04/05 must
be used
Momentary power loss
detection selection
n081
0
L2-01
0
n081 0
L2-01 0
n081 1
L2-01 1
n081 2
L2-01 2
Automatic restart
attempts
n082
0
L5-01
0
Jump frequency 1
n083
0.0 Hz
d3-01
0.0 Hz
Jump frequency 2
n084
0.0 Hz
d3-02
0.0 Hz
Jump frequency 3
n085
0.0 Hz
d3-03
0.0 Hz
Jump frequency
bandwidth
n086
0.0 Hz
d3-04
1.0 Hz
Operation time counter
selection
n087
0
o4-02
0
n087 0
o4-02 0
n087 1
o4-02 1
Accumulated operation
time
n088
0 H
o4-01
0 H
DC injection braking
current
n089
50%
b2-02
50%
DC injection time at stop
n090
0.5 sec
b2-04
o2-09
dep.
DC injection time at start
n091
0 sec
b2-03
0 sec
Stall prevention during
deceleration
n092
0
L3-04
1
n092 0
L3-04 1
n092 1
L3-04 0, 3
Stall prevention level
during acceleration
n093
170%
L3-02
150%
Stall prevention level
during run
n094
160%
L3-06
160%
Output frequency
detection level (DO)
n095
0.00 Hz
L4-01
0.0 Hz
Over / under torque
detection
n096
(OL)
n117
(UL)
0
L6-01
L6-03
0
n096,117 0
L6-01/03 0
n096,117 1
L6-01/03
1(OL),5(UL)
n096,117 2
L6-01/03
3(OL),6(UL)
n096,117 3
L6-01/03
2(OL),7(UL)
n096,117 4
L6-01/03
4(OL),8(UL)
Drive
Parameter
Function
V74X
V1000-4X
Note
Param.
No.
Initial
Value
Set
Value
Param.
No.
Initial
Value
Set
Value