3 ratings summary, Ratings summary – Yaskawa VS606 V74X V7 to V1000 User Manual
Page 6

Product Transition Guide
PL. V1000-4X.01 Rev: 6/22/10
PL.V1000-4X.01 Transition Guide 6/22/10
Page 6 of 32
Yaskawa America, Inc.
1.3 Ratings Summary
The following table summarizes the output current ratings for the V1000-
4X
and V7
4X
with respect to the specific drive
model. Please note that the V7
4X
current rating is based on a “Heavy Duty” rating, whereas, the V1000-
4X
factory default is
based on a “Normal Duty” rating. See below for an explanation of the differences between “Heavy” and “Normal” duty
ratings.
Note: If the V1000-4X drive is set to “Heavy Duty”, the current ratings are the same as the V74X drive.
Rated
Input Voltage
V74X Drive
Model Number
CIMR-V7CU
Heavy Duty
V1000-4X Drive
Model Number
CIMR-V
Normal Duty
Rated Output
Current (Amps)
Nominal HP
Rated Output
Current (Amps)
Nominal HP
200V,
3-Phase
20P14
20P24
20P44
0.8
1.6
3.0
1/8
1/4
1/2
2A0001GAA
2A0002GAA
2A0004GAA
1.2
1.9
3.5
1/8 & 1/4
1/4
1/2 & 3/4
20P74
21P54
5.0
8.0
3/4 & 1
2
2A0006GAA
2A0010GAA
6.0
9.6
1
2 & 3
22P24
23P74
11.0
17.5
3
5
2A0012GAA
2A0020GAA
12.0
19.6
3
5
25P54
27P54
25.0
33.0
7.5
10
2A0030GAA
2A0040GAA
30.0
40.0
7.5 & 10
10
400V,
3-Phase
40P24
40P44
1.2
1.8
1/2
3/4
4A0001GAA
4A0002GAA
1.2
2.1
1/2
3/4 & 1
40P74
41P54
3.4
4.8
1 & 2
3
4A0004GAA
4A0005GAA
4.1
5.4
2
3
42P24
43P74
45P54
5.5
8.6
14.8
3
5
7.5 & 10
4A0007GAA
4A0009GAA
4A0011GAA
6.9
8.8
11.1
4
5
7.5
45P54
47P54
14.8
18.8
7.5 & 10
10
4A0018GAA
4A0023GAA
18.0
24.0
10
15