Yaskawa VS606 V74X V7 to V1000 User Manual
Page 23

PL.V1000-4X.01 Transition Guide 6/22/10
Page 23 of 32
Yaskawa America, Inc.
Product Transition Guide
PL. V1000-4X.01 Rev: 6/22/10
Multi speed reference 12
n123
0.00 Hz
d1-12
0.00 Hz
Multi speed reference 13
n124
0.00 Hz
d1-13
0.00 Hz
Multi speed reference 14
n125
0.00 Hz
d1-14
0.00 Hz
Multi speed reference 15
n126
0.00 Hz
d1-15
0.00 Hz
Multi speed reference 16
n127
0.00 Hz
d1-16
0.00 Hz
PID control selection
n128
0
b5-01
0
V74X
V1000-4X
n128 0
b5-01 0
n128 1 b5-01 1
b5-09 0
n128 2 b5-01 2
n128 3 b5-01 3
PID output mode
selection
b5-09
0
n128 4 b5-01 4
n128 5 b5-01 1
b5-09 1
n128 6 b5-01 2
n128 7 b5-01 3
n128 8 b5-01 4
PID feedback gain
n129
1.0
H3-03
H3-11
H6-03
100%
Use feedback signal gain and bias
(analog, pulse input gain/bias)
PID proportional gain
(P)
n130
1.0
b5-02
1.00
PID integral time (I)
n131
1.0 sec
b5-03
1.0 sec
PID derivative time (D)
n132
0.0 sec
b5-05
0.0 sec
PID output offset
n133
0.0%
b5-07
0.0%
PID integral limit
n134
100%
b5-04
100%
PID output delay time
n135
0.0 sec
b5-08
0.0 sec
PID feedback loss
detection
n136
0
b5-12
0
n136 0
b5-12 0
n136 1
b5-12 1
n136 2
b5-12 2
PID feedback loss
detection level
n137
0%
b5-13
0%
PID feedback loss
detection time
n138
1.0 sec
b5-14
1.0 sec
Auto tuning selection
n139
0
T1-01
0
n139 0
b8-01 0
n139 1
b8-01 1
Energy saving
coefficient
n140
b8-04
o2-04
dep.
Value is different than V74X and
capacity dependent
Energy saving voltage
lower limit (60Hz)
n141
50%
-
-
No need to set.
Energy saving voltage
lower limit (6Hz)
n142
12%
-
-
Power average time
n143
1
-
-
Energy saving voltage
search limit
n144
0%
b8-06
0%
Voltage step width at
100% voltage
n145
0.5%
No need to set.
Voltage step width at
50% voltage
n146
0.1%
Drive
Parameter
Function
V74X
V1000-4X
Note
Param.
No.
Initial
Value
Set
Value
Param.
No.
Initial
Value
Set
Value