Yaskawa VS606 V74X V7 to V1000 User Manual
Page 20

Product Transition Guide
PL. V1000-4X.01 Rev: 6/22/10
PL.V1000-4X.01 Transition Guide 6/22/10
Page 20 of 32
Yaskawa America, Inc.
Analog output AM
function selection
n066
0
H4-01
102
V74X
V1000-4X
n066 0
H4-01 102
n066 1
H4-01 103
n066 2
H4-01 107
n066 3
H4-01 109
n066 4
H4-01 108
n066 5
H4-01 106
n066 6
H4-01 101
Analog output AM gain
n067
1.00
H4-02
100.0%
Analog frequency ref.
gain (Volt. input CN2)
Terminal A2 gain
n068
100%
H3-11
100.0%
H3-09 must be set to 0 or 1
Analog freq. reference
bias (Volt. input CN2)
Terminal A2 bias
n069
0%
H3-12
0.0%
Analog frequency ref.
filter (Volt. input CN2)
n070
0.10s
H3-13
0.03
Filter time H3-13 is the same for analog
input A1 and A2 in V1000-4X
Analog frequency ref.
gain (Cur. input CN2)
Terminal A2 gain
n071
100%
H3-11
100.0%
H3-09 must be set to 2 or 3
Analog frequency ref.
bias (Cur. input CN2)
Terminal A2 gain
n072
0%
H3-12
0.0%
Analog frequency ref.
filter (Volt. input CN2)
n073
0.10s
H3-13
0.03
Filter time H3-13 is the same for analog
input A1 and A2 in V1000-4X
Pulse input gain
n074
100%
H6-03
100.0%
Pulse input bias
n075
0%
H6-04
0.0%
Pulse input filter time
n076
0.10 sec
H6-05
0.10 sec
Analog input function
selection (CN2
Terminal A2)
n077
0
H3-10
0
n077 0
H3-10 F
n077 1
H3-10 2
n077 2
H3-10 1
n077 3
H3-10 0
n077 4
H3-10 4
Analog input signal level
selection (CN2
Terminal A2)
n078
0
H3-09
1
n078 0
H3-09 0
n078 1
H3-09 2
Frequency reference bias
max. value for terminal
CN2 reference input
terminal A2
n079
10%
-
-
This function can not be used with
current input in the V1000-4X.
For voltage input at terminal A2 the
following has to be set:
H3-09 1
H3-10 0
H3-11 n079
H3-11 -n079
Drive
Parameter
Function
V74X
V1000-4X
Note
Param.
No.
Initial
Value
Set
Value
Param.
No.
Initial
Value
Set
Value