beautypg.com

Yaskawa VS606 V74X V7 to V1000 User Manual

Page 17

background image

PL.V1000-4X.01 Transition Guide 6/22/10

Page 17 of 32

Yaskawa America, Inc.

Product Transition Guide

PL. V1000-4X.01 Rev: 6/22/10

Deceleration time 2

n022

10.0

sec

C1-04

10.0

sec

S-curve at accel. Start

n023

0 (0 sec)

C2-01

0.2 sec

In the V74X one of four values could be

selected for all s-curves. The V1000-4X

requires a separate time setting for each

s-curve.

S-curve at accel. End

n023

0 (0 sec)

C2-02

0.2 sec

S-curve at decel. start

n023

0 (0 sec)

C2-03

0.2 sec

S-curve at decel. end

n023

0 (0 sec)

C2-04

0.2 sec

Multi speed reference 1

n024

6.00 Hz

d1-01

o2-09,

FMAX

dep.

Multi speed reference 2

n025

0.00 Hz

d1-02

0 Hz

Multi speed reference 3

n026

0.00 Hz

d1-03

0 Hz

Multi speed reference 4

n027

0.00 Hz

d1-04

0 Hz

Multi speed reference 5

n028

0.00 Hz

d1-05

0 Hz

Multi speed reference 6

n029

0.00 Hz

d1-06

0 Hz

Multi speed reference 7

n030

0.00 Hz

d1-07

0 Hz

Multi speed reference 8

n031

0.00 Hz

d1-08

0 Hz

Jog frequency

n032

6.00 Hz

d1-17

6.00 Hz

Frequency reference

upper limit

n033

100%

d2-01

100.0%

Frequency reference

lower limit

n034

0%

d2-02

0.0%

Digital operator display

unit for frequency

reference values.

n035

0

o1-03

0

V74X

V1000-4X

n035 0

o1-03 0

n035 1

o1-03 1

n035 2~39

o1-03 2 and set

E2-04, E4-04,

E4-05

n035 40~3999

o1-03 3 and set

o1-10, o1-11

Motor rated current

n036

E2-01

kVA

dep.

Depends on the drive capacity

(V74X ,V1000-4X)

Motor overload

protection

n037

0

L1-01

1

n037 0

L1-01 1

n037 1

L1-01 2~4

n037 2

L1-01 0

Motor overload

protection time

n038

8 min

L1-02

1 min

Needs not to be changed.

Drive cooling fan

operation selection

n039

0

L8-10

0

n039 0

ÁÂÃÄÅ Å

n039 1

L8-10 1

Phase order selection

n040

0

b1-14

0

n040 0

b1-14 0

n040 1

b1-14 1

Acceleration Time 3

n041

10 sec

C1-05

10.0 sec

In V1000-4X also used as Accel Time 1

for Motor 2

Deceleration Time 3

n042

10 sec

C1-06

10.0 sec

In V1000-4X also used as Decel Time 1

for Motor 2

Acceleration Time 4

n043

10 sec

C1-07

10.0 sec

In V1000-4X also used as Accel Time 2

for Motor 2

Deceleration Time 4

n044

10 sec

C1-08

10.0 sec

In V1000-4X also used as Decel Time 2

for Motor 2

Drive

Parameter

Function

V74X

V1000-4X

Note

Param.

No.

Initial

Value

Set

Value

Param.

No.

Initial

Value

Set

Value