Yaskawa J7 to J1000 User Manual
Page 13

(Header Title) Application Note
Doc#: PL.J1000.01 Copyright Yaskawa Electric America, Inc.©2008 www.yaskawa.com August 1, 2008 13 of 19
Subject: Transition Guide
Product: J1000
Document: PL.J1000.01
Title: Product Transition Guide – J7 to J1000
Product Transition Guide – J7 to J1000
J7
J1000
Drive
Function
/ Parameter
Parameter
No.
Initial
Value
Parameter
No.
Initial
Value
Comments
Frequency Reference
from Operator ENTER
Key Selection
n08 0
o2-05 0
J7 J1000
n08 Æ 0
o2-05 Æ 0
n08 Æ 1
o2-05 Æ 1
Maximum Output
Frequency
n09
60.0 Hz
E1-04
60.0 Hz
—
Maximum Output
Voltage
n10
200.0V*
E1-05
200 V*
* Values for a 400 V class drive are double.
Base Frequency
n11
60.0 Hz
E1-06
60.0 Hz
—
Middle Output
Frequency
n12
1.5 Hz
E1-07
3.0 Hz
—
Middle Output Voltage
n13
12.0 V*
E1-08
16.0 V*
* Values for a 400 V class drive are double.
Minimum Output
Frequency
n14
1.5 Hz
E1-09
1.5 Hz
—
Minimum Output
Voltage
n15
12.0 V*
E1-10
12.0 V*
* Values for a 400 V class drive are double.
Acceleration Time 1
n16
10.0 s
C1-01
10.0 s
—
Deceleration Time 1
n17
10.0 s
C1-02
10.0 s
—
Acceleration Time 2
n18
10.0 s
C1-03
10.0 s
—
Deceleration Time 2
n19
10.0 s
C1-04
10.0 s
—
S –Curve at
Acceleration Start
C2-01
S-Curve at Acceleration
End
C2-02
S-Curve at Deceleration
Start
C2-03
0.2 s
S-Curve at Deceleration
End
n20
0 (0 s)
C2-04 0.0
s
J7:
Selection parameter (setting 0, 1, 2 and 3).
Same setting for all conditions.
J1000:
Numerical parameter (time must be set in
seconds). The S-Curve is set separately for
each accel / decel profile selection.
Multiple Speed Ref. 1
n21
6.00 Hz
d1-01
0.00 Hz
—
Multiple Speed Ref. 2
n22
0.00 Hz
d1-02
0.00 Hz
—
Multiple Speed Ref. 3
n23
0.00 Hz
d1-03
0.00 Hz
—
Multiple Speed Ref. 4
n24
0.00 Hz
d1-04
0.00 Hz
—
Multiple Speed Ref. 5
n25
0.00 Hz
d1-05
0.00 Hz
—
Multiple Speed Ref. 6
n26
0.00 Hz
d1-06
0.00 Hz
—
Multiple Speed Ref. 7
n27
0.00 Hz
d1-07
0.00 Hz
—
Multiple Speed Ref. 8
n28
0.00 Hz
d1-08
0.00 Hz
—
Jog Frequency
n29
6.00 Hz
d1-17
6.00 Hz
—
Frequency Reference
Upper Limit
n30 100%
d2-01 100%
—
Frequency Reference
Lower Limit
n31 0%
d2-02
0.0%
—
Motor Rated Current
n32 —
E2-01 —
Depends on the drive capacity.
Motor Overheat
Protection
n33 0
L1-01 1
J7 J1000
n33 Æ 0
L1-01 Æ 1
n33 Æ 1
L1-01 Æ 2
n33 Æ 2
L1-01 Æ 0