NOTES:

(1)

Based on an N.E.C. standard 4-pole motor for max. applicable motor output.

(2)

Shows deceleration torque for an uncoupled motor decelerating from 60 Hz in 0.1 seconds.

(3)

Contact Yaskawa for wiring distances greater than 328 ft. (100 m).

(4)

Temperature during shipping (for short periods of time).

(5)

On NEMA type 4X/12 model only, maximum continuous rating of 30.8 A is 40 degrees C maximum ambient. For 33.0 A maximum
continuous rating, maximum ambient is 32 degrees C.

(6)

Applies to NEMA type 4X/12 model only.

(7)

On Model 47P5 NEMA type 4X/12 (21A), overload is 120% for 1 minute.

SECTION B. All Drives (Continued)

Open Loop Vector Control, full-range automatic torque boost, auto restart,

Standard functions

upper/lower frequency limit, DC injection braking current/time at start/stop,

frequency reference gain/bias, prohibited frequencies,

analog meter calibrating gain, S-curve accel/decel, slip compensation,

MODBUS communications (RS485/422, Max. 19.2K bps),

frequency reference from digital operator pot

Status indicator LEDs

RUN and ALARM LEDs provided as standard

Digital Operator

Monitors frequency reference, output frequency,

output current, FWD/REF selection

Terminals

Screw terminals for both main circuit and control circuit

Wiring distance between
drive and motor

328 ft (100 m) or less

(3)

Enclosure

Open Type/NEMA type 1/NEMA type 4X/12

Cooling method

Self-cooling/cooling fan

Ambient temperature

14 to 104°F (-10 to 40°C)

Humidity

95% RH or less (non-condensing)

Storage temperature

(4)

-4 to 140°F (-20 to 60°C)

Location

Indoor (free from corrosive gases or dust)

Elevation

3,280 feet (1,000 m) or less

Vibration

Up to 1G, at less than 20 Hz;

up to 0.2G, at 20 to 50 Hz

En

vironmental

conditions

Other Functions