Drive Parameter Listing
(n001-n004)

Section 8

The Drive control circuits use various parameters to select functions and characteristics of the Drive. Changing of parameter
settings must be done in the Program mode, or by use of the Function LEDs, if available (see TM.V7.01, Section 4).

The following table lists all parameters in numerical order. For each parameter, reference paragraph(s) in TM.V7.01, Section
5 are listed (if applicable) where the features of the Drive affected by that parameter are described.

PARA-

SETTING RANGE

SETTING

FACTORY

USER

PARA.

METER

NAME

(AND UNITS)

INCREMENT

SETTING

SETTING

REF.

0:

n001 can be read and set;
n002 - n179 read only

1:

n001 - n039 can be read and set

2:

n001 - n079 can be read and set

3:

n001 - n119 can be read and set

n001

Parameter Selection /

4:

n001 - n179 can be read and set

Initialization

5:

n001 - n179 can be read and set

1

1

5.21

Run command accepted during Program

mode

6:

Clear Fault History Only

7:

Not Used

8:

2-wire Initialization (Japan Spec.)

9:

3-wire Initialization (Japan Spec.)

10: 2 wire initialization (USA Spec)
11: 3 wire initialization (USA Spec.)

n002

Control Method Selection

0:

V/f Control

1

0

2.2

1:

Open Loop Vector

0:

Digital Operator

n003

Operation Method Selection

1:

Terminal

1

1

5.13

2:

Serial Communication (Modbus)

3:

Option Card

0:

Digital Operator Pot

1:

Digital Operator

2:

Voltage Reference (0 to 10V)

3:

Current Reference (4 to 20 mA)

n004

Reference Selection

4:

Current Reference (0 to 20 mA)

5.11,

5:

Pulse Train Reference

1

2

5.13

6:

Serial Communications (Modbus)

7:

Multi-Function Analog Input (0 to 10V)

8:

Multi-Function Analog Input (4 to 20 mA)

9:

Option Card