Drive parameter listing, Drive parameter listing (n001-n004) – Yaskawa V74X Drives User Manual
Page 36

Drive Parameter Listing
(n001-n004)
Section 8
The Drive control circuits use various parameters to select functions and characteristics of the Drive. Changing of parameter
settings must be done in the Program mode, or by use of the Function LEDs, if available (see TM.V7.01, Section 4).
The following table lists all parameters in numerical order. For each parameter, reference paragraph(s) in TM.V7.01, Section
5 are listed (if applicable) where the features of the Drive affected by that parameter are described.
PARA-
SETTING RANGE
SETTING
FACTORY
USER
PARA.
METER
NAME
(AND UNITS)
INCREMENT
SETTING
SETTING
REF.
0:
n001 can be read and set;
n002 - n179 read only
1:
n001 - n039 can be read and set
2:
n001 - n079 can be read and set
3:
n001 - n119 can be read and set
n001
Parameter Selection /
4:
n001 - n179 can be read and set
Initialization
5:
n001 - n179 can be read and set
1
1
5.21
Run command accepted during Program
mode
6:
Clear Fault History Only
7:
Not Used
8:
2-wire Initialization (Japan Spec.)
9:
3-wire Initialization (Japan Spec.)
10: 2 wire initialization (USA Spec)
11: 3 wire initialization (USA Spec.)
n002
Control Method Selection
0:
V/f Control
1
0
2.2
1:
Open Loop Vector
0:
Digital Operator
n003
Operation Method Selection
1:
Terminal
1
1
5.13
2:
Serial Communication (Modbus)
3:
Option Card
0:
Digital Operator Pot
1:
Digital Operator
2:
Voltage Reference (0 to 10V)
3:
Current Reference (4 to 20 mA)
n004
Reference Selection
4:
Current Reference (0 to 20 mA)
5.11,
5:
Pulse Train Reference
1
2
5.13
6:
Serial Communications (Modbus)
7:
Multi-Function Analog Input (0 to 10V)
8:
Multi-Function Analog Input (4 to 20 mA)
9:
Option Card
V7 Parameters
36
IG.V7.01_new format.qxd:IG.V7.01_new format.qxd 8/21/07 2:24 PM Page 36