Drive parameter listing (n141-n151) – Yaskawa V74X Drives User Manual
Page 47

Drive Parameter Listing
(n141-n151)
Section 8
PARA-
SETTING RANGE
SETTING
FACTORY
USER
PARA.
METER
NAME
(AND UNITS)
INCREMENT
SETTING
SETTING
REF.
Energy Saving Voltage
0 to 120
1%
50
n141
Lower Limit at 60 Hz
(Energy Saving)
Energy Saving Voltage
0 to 25
1%
12
n142
Lower Limit at 6 Hz
(Energy Saving)
5.31
n143
Time of Average kW
1 to 200
1
1
(Energy Saving)
(x 24 ms)
(24 ms)
n144
Voltage Limit of Tuning
1 to 100
1%
0
(Energy Saving)
n145
Step Voltage of Tuning to
100% Output Voltage
0.1 to 10.0
0.1%
0.5
(Energy Saving)
n146
Step Voltage of Tuning to
5% Output Voltage
0.1 to 10.0
0.1%
0.2
(Energy Saving)
n149
Pulse Train Input Scaling
100 to 3300
1 (x 10 Hz)
3072
5.11
(30,720 Hz)
Output Frequency Monitor:
0:
1440 Hz / Max. output frequency
1:
1f output
6:
6f output
12: 12f output
24: 24f output
0, 1, 6, 12,
n150
Pulse Monitor Output
36: 36f output
24, 36, 40,
0
5.17
Frequency Selection
Frequency Reference Monitor:
41, 42, 43,
40: 1440Hz / Max. output frequency
44, 45
41: Frequency reference * 1
42: Frequency reference * 6
43: Frequency reference * 12
44: Frequency reference * 24
45: Frequency reference * 36
0:
Fault - Coast to stop
1:
Fault - Ramp to stop (n020)
n151
Modbus Time Out
2:
Fault - Ramp to stop (n022)
1
0
5.14
Detection
3:
Alarm - operation continues
4:
Disabled
Drive Parameters - Continued
47
IG.V7.01_new format.qxd:IG.V7.01_new format.qxd 8/21/07 2:24 PM Page 47