Drive parameter listing (n141-n151) – Yaskawa V74X Drives User Manual

Page 47

background image

Drive Parameter Listing

(n141-n151)

Section 8

PARA-

SETTING RANGE

SETTING

FACTORY

USER

PARA.

METER

NAME

(AND UNITS)

INCREMENT

SETTING

SETTING

REF.

Energy Saving Voltage

0 to 120

1%

50

n141

Lower Limit at 60 Hz
(Energy Saving)

Energy Saving Voltage

0 to 25

1%

12

n142

Lower Limit at 6 Hz
(Energy Saving)

5.31

n143

Time of Average kW

1 to 200

1

1

(Energy Saving)

(x 24 ms)

(24 ms)

n144

Voltage Limit of Tuning

1 to 100

1%

0

(Energy Saving)

n145

Step Voltage of Tuning to
100% Output Voltage

0.1 to 10.0

0.1%

0.5

(Energy Saving)

n146

Step Voltage of Tuning to
5% Output Voltage

0.1 to 10.0

0.1%

0.2

(Energy Saving)

n149

Pulse Train Input Scaling

100 to 3300

1 (x 10 Hz)

3072

5.11

(30,720 Hz)

Output Frequency Monitor:

0:

1440 Hz / Max. output frequency

1:

1f output

6:

6f output

12: 12f output
24: 24f output

0, 1, 6, 12,

n150

Pulse Monitor Output

36: 36f output

24, 36, 40,

0

5.17

Frequency Selection

Frequency Reference Monitor:

41, 42, 43,

40: 1440Hz / Max. output frequency

44, 45

41: Frequency reference * 1
42: Frequency reference * 6
43: Frequency reference * 12
44: Frequency reference * 24
45: Frequency reference * 36

0:

Fault - Coast to stop

1:

Fault - Ramp to stop (n020)

n151

Modbus Time Out

2:

Fault - Ramp to stop (n022)

1

0

5.14

Detection

3:

Alarm - operation continues

4:

Disabled

Drive Parameters - Continued

47