Drive parameter listing (n096-n109) – Yaskawa V74X Drives User Manual
Page 44

Drive Parameter Listing
(n096-n109)
Section 8
PARA-
SETTING RANGE
SETTING
FACTORY
USER
PARA.
METER
NAME
(AND UNITS)
INCREMENT
SETTING
SETTING
REF.
0:
Detection Disabled
1:
Detect only at set frequency;
operation continues
2:
Detect only at set frequency;
n096
Overtorque Detection (OL3)
coast to stop
1
0
3:
Detect during all frequency conditions;
operation continues
4:
Detect during all frequency conditions;
coast to stop
5.20
Overtorque Detection
n097
Selection (OL3)
0:
Detected by output torque
1
0
(Note 5)
1:
Detected by output current
n098
Overtorque Detection
Level (OL3)
30 to 200
1 (%)
160
n099
Overtorque Detection
Delay Time (OL3)
0.1 to 10.0
0.1 (sec)
0.1 (sec)
0.1 (sec)
0.1
n100
Up/Down Hold
0:
Disabled
Memory
1:
Enabled
1
0
5.10
n101
Speed Search
Deceleration Time
0.0 to 10.0
2
5.18
n102
Speed Search Operation
Level
0 to 200%
1 (%)
150
5.18
n103
Torque Compensation Gain
0.0 to 2.5
0.1
1.0
(Note 4)
n104
Torque Compensation
5.26
Time Constant
0.0 to 25.5
(Note 2)
n105
Torque Compensation
0.1 (W) or
Iron Loss
0.0 to 6550
1 (W)
(Note 1)
n106
Motor Rated Slip (Note 4)
0.0 to 20.0
0.1 (Hz)
(Note 1)
2.2, 5.22
n107
Motor Line-to-line
0.001 (ohm)
Resistance
0.000 to 65.50
(Note 1)
n108
Motor Leakage
0.01 (mH)
Inductance (Note 1)
0.00 to 655.0
or 0.1 (mH)
(Note 1)
n109
Torque Compensation
1 (%)
Limit (Note 5)
0 to 250
150
5.26
Drive Parameters - Continued
44