Drive Parameter Listing
(n059-n069)
Section 8
PARA-
SETTING RANGE
SETTING
FACTORY
USER
PARA.
METER
NAME
(AND UNITS)
INCREMENT
SETTING
SETTING
REF.
14: During auto restart
Multi-Function Output
15: During undervoltage
n059
Selection 3
16: During reverse run
(Terminals P2 & PC)
17: During speed search
1
2
18: Serial Comm. Controlled
19: PID feedback loss
20: Frequency Reference Loss Detect (N.O.)
``
21: Overheat Pre-alarm OH3 (N.O.)
n060
Analog Frequency Reference
0 to 255
1 (%)
100
Gain (term. FR to FC) (Note 4)
5.8
n061
Analog Frequency Reference
-100 to 100
1 (%)
0
Bias (term. FR to FC) (Note 4)
n062
Analog frequency reference
filter time constant
0.00 to 2.00
0.01 (sec)
0.10
(term. FR to FC) (Note 4)
n064
Frequency Reference Loss
0:
No Detection
1
0
5.33
Detection
1:
Continue to run at 80% of max. frequency
n065
Monitor Output
0:
Analog monitor output
1
0
5.17
Selection
1:
Pulse monitor output
0:
Output frequency (10V = 100% Fmax)
1:
Output Current (10V = 100% drive
rated current)
2:
DC Bus Voltage
n066
Multi-function Analog Output
(10V = 400 VDC [800 VDC])
(Terminals AM & AC)
3:
Motor Torque
1
0
5.17
(10V = Motor rated torque)
4:
Output Power
(10V = Drive Capacity kW)
5:
Output Voltage 10V = n012 (voltage max)
6:
Frequency Reference
n067
Analog Monitor Gain (Note 4)
0.00 to 2.00
0.01
1.00
n068
Analog Frequency Reference
-255 to 255
1%
100
Gain (CN2, Voltage Ref Input)
n069
Analog Frequency Reference
-100 to 100
1%
0
5.32
Bias (CN2, Voltage Ref Input)