Drive Parameter Listing

(n080-n095)

Section 8

PARA-

SETTING RANGE

SETTING

FACTORY

USER

PARA.

METER

NAME

(AND UNITS)

INCREMENT

SETTING

SETTING

REF.

n080

Carrier Frequency

1 to 4 (x 2.5 kHz)

1

3

5.5

7 to 9 (synchronous)

0:

Not Provided

1:

Continuous operation after power

n081

Momentary Power Loss

recovery within 2 sec.

Ride-through Method

2:

Continuous operation after power

1

0

5.16

recovery within control logic time
(no fault output)

n082

Number of auto restarts

0 to 10

1

0

5.4

attempts

n083

Prohibit Frequency 1

0.00 to 400.0

0.01 (Hz)

0.00

or 0.1 (Hz)

n084

Prohibit Frequency 2

0.00 to 400.0

0.01 (Hz)

0.00

5.6

or 0.1 (Hz)

n085

Prohibit Frequency 3

0.00 to 400.0

0.01 (Hz)

0.00

or 0.1 (Hz)

n086

Prohibit Frequency Deadband 0.00 to 25.50

0.01 (Hz)

0.00

n089

DC Injection Current

0 to 100

1 (%)

50

n090

DC Injection Time at stop

0.0 to 25.5

0.1 (sec)

0.0

5.7

n091

DC Injection Time at start

0.0 to 25.5

0.1 (sec)

0.0

n092

Stall Prevention During

0:

Enabled

1

0

Deceleration

1:

Disabled

n093

Stall Prevention During

30 to 200

1 (%)

170

5.23

Acceleration

n094

Stall Prevention Level During

30 to 200

1 (%)

160

Running

n095

Frequency Detection Level

0.00 to 400.0

0.01 (Hz)

0.00

5.19

Drive Parameters - Continued

43