Drive parameter listing (n080-n095), Drive parameters - continued – Yaskawa V74X Drives User Manual
Page 43

Drive Parameter Listing
(n080-n095)
Section 8
PARA-
SETTING RANGE
SETTING
FACTORY
USER
PARA.
METER
NAME
(AND UNITS)
INCREMENT
SETTING
SETTING
REF.
n080
Carrier Frequency
1 to 4 (x 2.5 kHz)
1
3
5.5
7 to 9 (synchronous)
0:
Not Provided
1:
Continuous operation after power
n081
Momentary Power Loss
recovery within 2 sec.
Ride-through Method
2:
Continuous operation after power
1
0
5.16
recovery within control logic time
(no fault output)
n082
Number of auto restarts
0 to 10
1
0
5.4
attempts
n083
Prohibit Frequency 1
0.00 to 400.0
0.01 (Hz)
0.00
or 0.1 (Hz)
n084
Prohibit Frequency 2
0.00 to 400.0
0.01 (Hz)
0.00
5.6
or 0.1 (Hz)
n085
Prohibit Frequency 3
0.00 to 400.0
0.01 (Hz)
0.00
or 0.1 (Hz)
n086
Prohibit Frequency Deadband 0.00 to 25.50
0.01 (Hz)
0.00
n089
DC Injection Current
0 to 100
1 (%)
50
n090
DC Injection Time at stop
0.0 to 25.5
0.1 (sec)
0.0
5.7
n091
DC Injection Time at start
0.0 to 25.5
0.1 (sec)
0.0
n092
Stall Prevention During
0:
Enabled
1
0
Deceleration
1:
Disabled
n093
Stall Prevention During
30 to 200
1 (%)
170
5.23
Acceleration
n094
Stall Prevention Level During
30 to 200
1 (%)
160
Running
n095
Frequency Detection Level
0.00 to 400.0
0.01 (Hz)
0.00
5.19
Drive Parameters - Continued
43
IG.V7.01_new format.qxd:IG.V7.01_new format.qxd 8/21/07 2:24 PM Page 43