I Limit
P2-05=2.000 HZ
P2-05 Integral
Limit
Q Q Q Q
This parameter limits the integral part of the position regulator. This parameter should be increased when the
drive will not stay shaft-locked under heavy loads or at high speeds (above base speed). Too high of a setting
will result in instability or overshoot.
D Time
P2-06 = 0.00 sec
P2-06 Derivative
Time
Q Q Q Q
This parameter provides control of the derivative function of the PID speed control loop. Setting this value to zero
will remove any affect that it may have. The derivative provides a means to stabilize the position error if it is
oscillating between plus and minus. Setting this value to high will cause instability.
5.0 New Monitors
Master Encoder
U1-50= 0.00 kHZ
U1-50 Master
Encoder
Q Q Q Q
Displays the pulse frequency of the master encoder.
Slave Reference
U1-51= 0.0 HZ
U1-51 Slave
Reference
Q Q Q Q
Displays the frequency reference of the follower drive prior to ratio adjustments. The follower will not exceed its
maximum output frequency based on E1-04 and D2-01.
Setting Range:
0.000 to 20.000
Factory Default:
2000
MODBUS Address:
0594H
Setting Range:
0.00 to 100.00
Factory Default:
0.00
MODBUS Address:
0595H
Range:
0.00 to 327.67 kHz
MODBUS Address:
00D0H
Range:
-999.9 to 3276.7 Hz
MODBUS Address:
00D1H