4.8 Alarms
Alarm Display
Description
Cause
Countermeasures
FDEV
Follower Pos
Dev
The position error has
exceeded the Follower
Deviation Level (P2-06)
and the Follower Deviation
Selection (P2-07) is set to
1 (Alarm Only).
Mechanical
binding of
the follower motor.
The Follower Deviation
Level (P2-06) is too low.
The master encoder is
rotating, the follower
drive is stopped, and the
Position Error
Accumulation Selection
(P1-09) is set to 1 (error
is always accumulated).
The master input
frequency is greater than
the follower maximum
frequency (E1-04).
Confirm the machinery
is operating correctly
and the follower motor
is not binding.
Increase P2-06.
If the application
requires that the master
encode rotate while the
follower is stopped, set
P1-09 = 0 (position
error only during run).
Set E1-04 to 10% faster
than the maximum
master input frequency.