10 Troubleshooting
YASKAWA SIEP YEACOM 07A 1000-Series Option PROFINET SI-EP3 Technical Manual
55
Option Fault Monitors U6-98 and U6-99
The option can declare error/warning conditions via drive monitor parameters on the drive digital operator as shown in
.
Table 32 Option Fault Monitor Descriptions
Two drive monitor parameters, U6-98 and U6-99 assist in network troubleshooting:
• U6-98 displays the first declared fault since the last power cycle. U6-98 is only cleared upon drive power-up.
• U6-99 displays the present option SI-EP3 status. U6-99 is cleared upon a network-issued fault reset and upon
power-up.
If another fault occurs while the original fault is still active, parameter U6-98 retains the original fault value and U6-99
stores the new fault status value.
Option Compatibility
A limited number of options may be simultaneously connected to the drive depending on the type of option. Refer to
for more information. More details can be found in the Options and Peripheral Devices chapter of the drive
Technical Manual.
Table 33 Option Installation Compatibility
Fault Condition
Fault Declared
Status Value
(U6-98/U6-99)
Description
No Fault
n/a
0
No faults.
Force Fault
EF0
3
Network sent a message to force this node to the fault state.
Network Link Down
BUS ERROR
1300
No network link to option board.
Network Failure
BUS ERROR
1301
Connection with PLC Timeout.
Default MAC Address
None
1303
Factory default MAC Address programmed into the option. Return for
reprogramming.
No IP Address
None
1304
No IP Address has been programmed into the option.
No Station Name
None
1305
No Station Name has been programmed into the option.
Config Error
None
1306
Configuration error on power-up.
Init. Failure
None
1307
Initialize error on power-up.
Permanent
Communication Loss
BUS ERROR
1308
Fatal error in MAC/PHY hardware, requires power cycle to recover.
Option
<1> When installed in CN5-A, the AI-A3 and DI-A3 options can be used to set the frequency reference or replace the drive analog inputs with higher
resolution. When installed in CN5-B or CN5-C, these options can only be used for monitoring; their input levels will be displayed in U1-17 or
U1-21 to U1-23.
<2> Use the CN5-C connector when connecting only one option to the drive; use both CN5-B and CN5-C when connecting two options.
Connector
Number of Possible Options
SI-C3, SI-N3, SI-P3, SI-S3, SI-EP3, SI-EN3, SI-EM3
CN5-A
1
PG-B3, PG-X3
CN5-B, C
2
DO-A3, AO-A3, AI-A3, DI-A3
CN5-A, B, C
1