Yaskawa PROFINET User Manual
Page 34

8 Communication
34
YASKAWA SIEP YEACOM 07A 1000-Series Option PROFINET SI-EP3 Technical Manual
Parameter Data Transfer Examples
The following example shows how parameter data is transferred using the acyclic parameter access mechanism's READ
and WRITE.
Example 1: Reading a drive parameter
To read a Yaskawa Drive parameter, use the PNU of 1 and the actual address of the parameter in the SubIndex.
Write Request (Read Parameter Value)
Positive Read Response to Read Request
PROFIdrive compatible Parameter Channel
0x65 Vendor-specific
error
Vendor-specific error
0x66
Request not supported
Request not supported
0x67 Communication
error
Request
cannot be completed because of communication error
0x6F Time-out
error
Request
aborted due to time-out
0x78
PZD map failure
Parameter cannot be mapped to PZD (size mismatch or non-existent)
0x79
PZD memory failure
Parameter cannot be mapped to PZD (out of memory)
0x7A
Multiple PZD map
Parameter cannot be mapped to PZD (multiple PZD write)
0x8C
Set torque mode error
Cannot change mode to TORQUE (frequency is used)
0x90
Illegal Request ID
The request ID of the response is illegal
Error #
Meaning
Used at