beautypg.com

Identification and maintenance functions (i&m), Diagnostic and alarms, Alarm mechanism – Yaskawa PROFINET User Manual

Page 39

background image

8 Communication

YASKAWA SIEP YEACOM 07A 1000-Series Option PROFINET SI-EP3 Technical Manual

39

‹

Identification and Maintenance Functions (I&M)

The purpose of the I&M functions is to provide support for the customer during commissioning, parametrization and
repair of the module. SI-EP3 supports I&M function 0, which can be accessed using the Record data object's read request.

Structure of the I&M functions is described in the following tables.

Table 26 I&M0 Device Identification (Read-Only)

‹

Diagnostic and Alarms

SI-EP3 has mechanisms for sending alarms and saving diagnostics data to fault buffer. Alarm will be triggered if the host
or drive has faults in communication or operation. There are three types of faults:

‹

Alarm Mechanism

When a fault or alarm situation occurs in the drive, the SI-EP3 adapter will send an alarm notification, which the master
station must acknowledge. Refer to

Table 27

for details.

Table 27 Alarm Notification

Function

Record Data Index

I&M0

0xAFF0

Content

Size

Description

Header 10

bytes

-

Vendor ID

2 bytes

PROFINET Vendor ID of Yaskawa, which is 0x019F

Order ID

20 bytes

Order number of the SI-EP3 adapter kit (SI-EP3)

Serial number

16 bytes

Serial number of the adapter

Hardware revision

2 bytes

Hardware revision of the SI-EP3 adapter

Software revision

4 bytes

Revision of the software

Revision counter

2 bytes

Number of revision

Profile ID

2 bytes

(0x0000)

Profile specific type

2 bytes

No profile specific type (0x0000)

I&M version

2 bytes

Version is 1.1 (0x0101)

Supported I&M functions

2 bytes

I&M0 is supported (0x0001)

Fault

API/Slot/Sub-slot

Channel Error Type

Drive Fault

0/1/1

A fault declared in drive

Attribute

Description

BlockHeader

-

AlarmType

PROFINET specific alarm type

API 0

(PROFIdrive

profile)

SlotNumber

Slot number of the Drive Object (DO)

SubslotNumber Sub-slot

number

of the sub-slot to which the diagnosis object is related

ModuleIdentNumber Module

Ident number of the DO

SubmoduleIdentNumber 0xFFFF
AlarmSpecifier Diagnosis

type

UserStructureIdentifier 0x8000 (Channel Diagnosis Data)
ChannelNumber 0

ChannelProperties

0x0800 Diagnosis Appears
0x1000 Diagnosis Disappears

ChannelErrorType Error

code

of drive fault or drive alarm

This manual is related to the following products: