7 PROFINET Messaging

YASKAWA SIEP YEACOM 07A 1000-Series Option PROFINET SI-EP3 Technical Manual

25

‹

Yaskawa Vendor-Specific Control and Status Words

„

The Control Word and the Status Word

The contents of the Control Word and the Status Word are detailed in

Table 10

.

„

Frequency Reference

Frequency Reference is a 16-bit word containing the desired output frequency.

„

Output Frequency

Output Frequency is a 16-bit word containing the current output frequency of the drive.

Table 10 Yaskawa-Specific Control Word and Status Word

Yaskawa-Specific Control Word

Yaskawa-Specific Status Word

Bit

Description

Bit

Description

0

Run bit

0

Running

1

Reverse run bit

1

Zero Speed

2

EF0

2

Reverse Operation

3

Fault Reset

3

Reset Signal Input Active

4

ComFref

4

At Speed

5

ComCtrl

5

Ready

6

DI3

6

Alarm

7

DI4

7

Fault

8

DI5

8

oPE Fault

9

DI6

9

Uv Return

10

DI7

10

2nd Motor

11

DI8

<1>

<1> Not available in V1000-series drives.

<2> Not available in A1000-series drives.

11

ZSV

12

DI9

<1> <2>

12

(Unused)

13

DI10

<1> <2>

13

(Unused)

14

DI11

<1> <2>

14

Net Reference

15

DI12

<1> <2>

15

Net Control