Yaskawa si-ep3 profinet i/o modules – Yaskawa PROFINET User Manual
Page 27
8 Communication
YASKAWA SIEP YEACOM 07A 1000-Series Option PROFINET SI-EP3 Technical Manual
27
Yaskawa SI-EP3 PROFINET I/O Modules
Std Tgm 1
Table 11 Std Tgm 1 Consume
Table 12 Std Tgm 1 Produce
Std Tgm 1 + 5 PZD
Table 13 Std Tgm 1 + 5 PZD Consume
Table 14 Std Tgm 1 + 5 PZD Produce
Bytes
Description
0
Control Word MSB
1
Control Word LSB
2
Frequency Reference MSB
3
Frequency Reference LSB
Bytes
Description
0
Status Word MSB
1
Status Word LSB
2
Output Frequency MSB
3
Output Frequency LSB
Bytes
Description
0
Control Word MSB
1
Control Word LSB
2
Frequency Reference MSB
3
Frequency Reference LSB
4
Configurable Output 1 MSB
5
Configurable Output 1 LSB
6
Configurable Output 2 MSB
7
Configurable Output 2 LSB
8
Configurable Output 3 MSB
9
Configurable Output 3 LSB
10
Configurable Output 4 MSB
11
Configurable Output 4 LSB
12
Configurable Output 5 MSB
13
Configurable Output 5 LSB
Bytes
Description
0
Status Word MSB
1
Status Word LSB
2
Output Frequency MSB
3
Output Frequency LSB
4
Configurable Input 1 MSB
5
Configurable Input 1 LSB
6
Configurable Input 2 MSB
7
Configurable Input 2 LSB
8
Configurable Input 3 MSB
9
Configurable Input 3 LSB
10
Configurable Input 4 MSB
11
Configurable Input 4 LSB
12
Configurable Input 5 MSB
13
Configurable Input 5 LSB