10 Troubleshooting

YASKAWA SIEP YEACOM 07A 1000-Series Option PROFINET SI-EP3 Technical Manual

53

„

Minor Faults and Alarms

„

bUS Error Auto-Reset

bUS Error Auto-Reset Function Description

bUS Error Auto-Reset when configured, allows the drive to automatically recover from a bUS error as a result of a
communication loss with the host.

A bUS Error will automatically reset under the following conditions.

• Network communication between the host and the drive is restored. (bUS error removed)
• bUS Error Auto-Reset is enabled as described in this section.

Enabling bUS Error Auto-Reset

Parameter F6-14

<1>

bUS Error Auto Reset enables the bUS Error Auto-Reset function.

F6-14 becomes available when the option is installed on the drive.

1. Set parameter F6-14 = 1:Enabled
2. Set parameter F6-01 = 0:Ramp to Stop, 1:Coast to Stop, 2:Fast-Stop
3. Set parameter F7-16 = 0.1 to 10.0 seconds (optional)

Enabling bUS Error Auto-Restart (After a Time Delay)

Parameter F7-16 Communication Loss Timeout will delay the occurrence of a bUS error condition by the amount of
time set in this parameter. F7-16 is set in tenths of seconds. The status LEDs on the option will indicate the bUS error
condition immediately upon detection and during the F7-16 delay time. Refer to

Figure 23

.

• Set parameter F7-16 = 0.1 to 10.0 seconds (0.0 setting disables F7-16) to enable timeout delay.

LED Operator Display

Fault Name

oFc00

Option fault (CN5-C).
Non-compatible option is connected.

Cause

Possible Solution

Non-compatible option connected to the drive.

Connect the correct option to CN5-A.

LED Operator Display

Fault Name

oFc02

Option fault.
Option flash write mode.

Cause

Possible Solution

Options AI-A3 or DI-A3 are connected to the
CN5-B port with an option connected to CN5-A.

• Only one type of AI-A3 or DI-A3 option can be connected to the drive
• The SI-EP3 option can only be connected to CN5-A

LED Operator Display

Minor Fault Name

CALL

Serial communication transmission error.
Communication is not established.

Cause

Possible Solution

Minor Fault

(H2-†† = 10)

Communication wiring is faulty, there is a short
circuit, or improper connection

Check for wiring errors:

• Correct the wiring
• Remove ground shorts and reconnect loose wires

YES

Programming error on the master side

Check communications at start-up and correct programming errors.

Communication circuitry is damaged.

• Perform a self-diagnostics check
• Replace the drive if the fault continues to occur

<1>

Available in SI-EP3 firmware version VST800251 and later. Refer to

Table 35

for specifics relating to your drive and drive software version.