YASKAWA ELECTRIC TOBP C730600 42C 1000-Series Option SI-P3 Installation Manual

6 Related Parameters

6

Related Parameters

The following parameters are used to set up the drive for operation with the option.
Confirm proper setting of all parameters in

Table 8

before starting network communications.

Table 8 Related Parameters

No.

(Addr.

Hex)

Name

Description

Values

b1-01

(180)

<1>

Frequency Reference Selection 1

Selects the frequency reference input source
0: Operator - Digital preset speed d1-01 to d1-17
1: Terminals - Analog input terminal A1 or A2
2: MEMOBUS/Modbus communications
3: Option
4: Pulse Input (Terminal RP)

Default: 1
Range: 0 to 4
(Set to 3 for
SI-P3)

b1-02

(181)

<1>

Run Command Selection 1

Selects the run command input source
0: Digital Operator - RUN and STOP keys
1: Digital input terminals S†
2: MEMOBUS/Modbus communications
3: Option

Default: 1
Range: 0 to 3
(Set to 3 for
SI-P3)

F6-01
(3A2)

Communications Error
Operation Selection

Determines drive response after a bUS error is
detected during communications with the option
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

<2>

Default: 1
Range: 0 to 3

F6-02
(3A3)

External Fault from Comm.
Option Detection Selection

Sets the condition for external fault detection (EF0)
0: Always detected
1: Detected only during operation

Default: 0
Range: 0, 1

F6-03
(3A4)

External Fault from Comm.
Option Operation Selection

Determines drive response for external fault input
(EF0) detection during PROFIBUS communication
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

<2>

Default: 1
Range: 0 to 3

F6-06
(3A7)

<3>

Torque Reference/Torque Limit
Selection from Comm. Option

0: Torque reference/torque limit via network
communications are disabled.

1:

Torque reference/torque limit via network

communications are enabled.

<4>

Default: 0
Range: 0, 1

F6-07
(3A8)

Multi-Step Speed Enable/
Disable Selection when NefRef/
ComRef is Selected

0: Multi-step speed reference disabled
(F7 functionality)
1: Multi-step speed reference allowed
(V7 functionality)

Default: 0
Range: 0, 1