6 related parameters, Arameters in, Table 8 – Yaskawa 1000 Series Drive Option - Profibus-DP Installation User Manual
Page 24: 6related parameters
24
YASKAWA ELECTRIC TOBP C730600 42C 1000-Series Option SI-P3 Installation Manual
6 Related Parameters
6
Related Parameters
The following parameters are used to set up the drive for operation with the option.
Confirm proper setting of all parameters in
before starting network communications.
Table 8 Related Parameters
No.
(Addr.
Hex)
Name
Description
Values
b1-01
(180)
Frequency Reference Selection 1
Selects the frequency reference input source
0: Operator - Digital preset speed d1-01 to d1-17
1: Terminals - Analog input terminal A1 or A2
2: MEMOBUS/Modbus communications
3: Option
4: Pulse Input (Terminal RP)
Default: 1
Range: 0 to 4
(Set to 3 for
SI-P3)
b1-02
(181)
Run Command Selection 1
Selects the run command input source
0: Digital Operator - RUN and STOP keys
1: Digital input terminals S
2: MEMOBUS/Modbus communications
3: Option
Default: 1
Range: 0 to 3
(Set to 3 for
SI-P3)
F6-01
(3A2)
Communications Error
Operation Selection
Determines drive response after a bUS error is
detected during communications with the option
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
Default: 1
Range: 0 to 3
F6-02
(3A3)
External Fault from Comm.
Option Detection Selection
Sets the condition for external fault detection (EF0)
0: Always detected
1: Detected only during operation
Default: 0
Range: 0, 1
F6-03
(3A4)
External Fault from Comm.
Option Operation Selection
Determines drive response for external fault input
(EF0) detection during PROFIBUS communication
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
Default: 1
Range: 0 to 3
F6-06
(3A7)
Torque Reference/Torque Limit
Selection from Comm. Option
0: Torque reference/torque limit via network
communications are disabled.
1:
Torque reference/torque limit via network
communications are enabled.
Default: 0
Range: 0, 1
F6-07
(3A8)
Multi-Step Speed Enable/
Disable Selection when NefRef/
ComRef is Selected
0: Multi-step speed reference disabled
(F7 functionality)
1: Multi-step speed reference allowed
(V7 functionality)
Default: 0
Range: 0, 1