5 Installation Procedure
YASKAWA ELECTRIC TOBP C730600 42C 1000-Series Option SI-P3 Installation Manual
19
6.
Connect the option to the network using PROFIBUS-DP-dedicated cables as shown
in
.
Connection Diagram
Figure 7
Figure 7 Option Connection Diagram
<1> The ground wire provided in the option shipping package must be connected during installation.
PROFIBUS-DP Termination
The option does not have a termination resistor. The termination resistance must be
set on the final drive in the network using a switch on the 9-pin D-sub connector.
Make sure that only the connector for the final drive in the network has a termination
resistor; communication problems may arise if any other network drive has a
termination resistor.
Use only the input side cable entry as shown in
when connecting both
ends of the network. Most 9-pin D-sub connectors have a function for disconnecting
the output side of the cable. Communication will not be possible between devices if
the connector is reversed. Most connectors have arrows indicating the input and
output sides.
Drive
9-pin D-sub Connector
Turn on the termination resistor
switch for the last node on the bus
SI-P3
RTS
DGND
VP
A-line
B-line
1B
1A
3
8
4
6
5
2B
2A
CN5-A
FE
<1>
PROFIBUS Cable
PROFIBUS Cable Connector
(Red)
(Green)
(Red)
(Green)
(Shell)
To PROFIBUS-DP
Master
To the next slave
(Shell)