5 Installation Procedure

YASKAWA ELECTRIC TOBP C730600 42C 1000-Series Option SI-P3 Installation Manual

19

6.

Connect the option to the network using PROFIBUS-DP-dedicated cables as shown
in

Figure 8

.

Connection Diagram

Figure 7

Figure 7 Option Connection Diagram

<1> The ground wire provided in the option shipping package must be connected during installation.

PROFIBUS-DP Termination

The option does not have a termination resistor. The termination resistance must be

set on the final drive in the network using a switch on the 9-pin D-sub connector.

Make sure that only the connector for the final drive in the network has a termination

resistor; communication problems may arise if any other network drive has a

termination resistor.

Use only the input side cable entry as shown in

Figure 8

when connecting both

ends of the network. Most 9-pin D-sub connectors have a function for disconnecting

the output side of the cable. Communication will not be possible between devices if

the connector is reversed. Most connectors have arrows indicating the input and

output sides.

Drive

9-pin D-sub Connector

Turn on the termination resistor
switch for the last node on the bus

SI-P3

RTS

DGND

VP

A-line

B-line

1B

1A

3

8

4

6

5

2B

2A

CN5-A

FE

<1>

PROFIBUS Cable

PROFIBUS Cable Connector

(Red)

(Green)

(Red)

(Green)

(Shell)

To PROFIBUS-DP
Master

To the next slave

(Shell)