7 troubleshooting, Minor faults and alarms – Yaskawa 1000 Series Drive Option - MECHATROLINK-II Installation User Manual
Page 29

7 Troubleshooting
YASKAWA ELECTRIC
TOBP C730600 50C YASKAWA 1000-Series Option SI-T3 Installation Manual
29
■
Minor Faults and Alarms
Operator Display
Minor Fault Name
AEr
Station Address Error
MECHATROLINK-II Option is set to an address outside the allowable setting range.
Cause
Possible Solution
Minor Fault
(H2- = 10)
Address outside the
specified address range
⇒
Set F6-20 to an address within the specified range.
YES
Operator Display
Minor Fault Name
CALL
Serial Communication Transmission Error
Communication has not yet been established.
Cause
Possible Solution
Minor Fault
(H2- = 10)
Communication wiring is
faulty, there is a short
circuit, or something is not
connected properly.
Check for wiring errors.
⇒
Correct the wiring.
⇒
Remove and ground shorts and reconnect loose wires.
YES
Programming error on the
master side
⇒
Check communications at start-up and correct programming
errors.
Communication circuitry is
damaged.
Perform a self-diagnostics check.
⇒
Replace the unit if the fault continues to occur.