Operator Display

Fault Name

E5

MECHATROLINK-II Watchdog Timer Error
The watchdog has timed out.

Cause

Possible Solution

Data has not been received

from the PLC, triggering the

watchdog timer.

Execute DISCONNECT or ALM_CLR, then issue a CONNECT command or

SYNC_SET command and proceed to phase 3.

Operator Display

Fault Name

EF0

External Fault Input from MECHATROLINK-II Option
The alarm function for an external device has been triggered.

Cause

Possible Solution

An external fault is being

sent from the master

controller (PLC).

Remove the cause of the external fault.

Reset the external fault input from the PLC device.

Problem with the PLC

program

Check the program used by the PLC and make the appropriate corrections.

Operator Display

Fault Name

oFA00

MECHATROLINK-II Option Fault (CN5-A)
MECHATROLINK-II Option is not properly connected.

Cause

Possible Solution

Non-compatible option

connected to the unit

Connect an option that is compatible with the unit.

When an option is installed to the energy-saving unit, check the option software

version is 6105 or later.

Operator Display

Fault Name

oFA01

MECHATROLINK-II Option Fault (CN5-A)
MECHATROLINK-II Option is not properly connected.

Cause

Possible Solution

Problem with the connectors

between the unit and

MECHATROLINK-II

Option

Turn the power off and check the connectors between the unit and

MECHATROLINK-II Option.

Operator Display

Fault Name

to

oFA30 to

oFA43

MECHATROLINK-II Option Fault (CN5-A)

Communication ID error

Cause

Possible Solution

MECHATROLINK-II

Option hardware fault

Replace the MECHATROLINK-II Option. Contact Yaskawa for assistance.