Mechatrolink-ii option led display, 4 mechatrolink-ii option components, Checking led operation – Yaskawa 1000 Series Drive Option - MECHATROLINK-II Installation User Manual
Page 12

4 MECHATROLINK-II Option Components
12
YASKAWA ELECTRIC
TOBP C730600 50C YASKAWA 1000-Series Option SI-T3 Installation Manual
◆
MECHATROLINK-II Option LED Display
The MECHATROLINK-II Option has four LEDs that indicate the option or communication
status.
■
Checking LED Operation
Table 4 LED Display
LED
Color
Display
Status
Remarks
RUN
Green
ON
Power supply on
SI-T3 has been successfully powered up
OFF
No power
• The unit has no power
• SI-T3 is not properly connected to the unit, or SI-T3 has
no power
• An internal, self-diagnostic error occurred in the SI-T3
ERR
Red
ON
Connection error
• SI-T3 is not properly connected to the unit
• Communication error
Flashing SI-T3 error
Error found during SI-T3's self-diagnostic check
OFF
Normal operation
• SI-T3 is properly connected to the unit
• Communication normal
TX
Green
ON
Sending data
Data is being sent (LED may appear to be flashing)
OFF
Not sending data
• No data is being sent
• During reset
RX
Green
ON
Receiving data
Data is being received (LED may appear to be flashing)
OFF
Not receiving data • No data is being received
• During reset