8 CC-Link Data Table
YASKAWA ELECTRIC TOBP C730600 44A YASKAWA AC Drive-Option Card CC-Link Installation Manual
27
◆
Remote Register
■
PLC
→ Drive
Table 8 Remote Register (PLC
→ Drive)
■
Drive
→ PLC
Table 9 Remote Register (Drive
→ PLC)
Remote
Register
Name
Description
Request Flag
RW
W0
Monitor
Code
Sets the code number of the items to be displayed by the
monitor.
RYC (Monitor Execute
Request)
RW
W1
Frequency
Setting
Indicates which value is to be used to set the frequency.
• RYD (Frequency
Reference 1)
• RYE (Frequency
Reference 2)
RW
W2
Command
Code
Sets the command code to execute functions such as the fault
reset, fault history, parameter read, and so on.
RYF (Command Code
Execute Request)
RW
W3
Write Data
Sets the value to be used along with RW
W2
(Command Code)
as needed.
Remote
Register
Name
Description
Check Flag
RW
R0
Monitor
Data
Monitor data is stored according to RW
W0
(Monitor Code).
RXC (while monitoring)
RW
R1
Output
Frequency
Output frequency has been set without any errors. Set in the
units specified by o1-03 (Frequency Reference Setting Units).
–
RW
R2
Response
Code
Sets 00H when there are no problems with RW
W2
(Command
Code) and RW
W3
(Write Data).
Sets 01H through 03H if an error occurs.
Response Code:
00h: Normal
01h: Write-mode error (attempted to write during run, etc.)
02h: Command code error
03h: Data setting range error
RXF (Command Code
Execute Complete)
RW
R3
Read Data
Data is set according to the command code.