8 cc-link data table – Yaskawa 1000 Series Drive Option - CC-Link Installation User Manual
Page 25

8 CC-Link Data Table
YASKAWA ELECTRIC TOBP C730600 44A YASKAWA AC Drive-Option Card CC-Link Installation Manual
25
Note: 1. If making frequent setting changes, use RYD (Frequency Reference 1 flag) for setting the register.
Using RYE (Frequency Reference 2 flag) too often can shorten the performance life of the drive's
internal memory.
2. Although RYE and RYF are triggered by the rising edge of the signal, they are otherwise enabled
depending on the value that is input.
When switching between monitors using RYC (Monitor Reference), RYC needs to be turned off and
then back on again after the monitor code has been changed.
RYE
Frequency
Reference 2
Sets the frequency in the remote register RW
W1
to
parameter d1-01 (Frequency Reference 1) and as the
drive’s main frequency reference at the same time.
Note: If the frequency reference is
set to be provided by the
operator
(i.e, b1-01 = 0), then switching
on RYE changes the frequency
reference.
All parameter settings are saved
when this flag is switched on.
Triggered by the rising edge of
the signal.
RYF
Command
Code Execute
Request
Request to execute the command code.
Triggered by the rising edge of
the signal.
RY10 to
13
Reserved
–
–
RY14
Terminal S1
Function
Multi-function input: H1-01
Function is disabled when for the
Forward Run Command (H1-01
= 40).
RY15
Terminal S2
Function
Multi-function input: H1-02
Function is disabled when for the
Reverse Run Command (H1-02 =
41).
RY16 to
19
Reserved
–
–
RY1A
Fault Reset
Resets a drive fault
–
RY1B to
1F
Reserved
–
–
Signal
Name
Description
Default