Connecting the AC output
To connect the AC output, proceed as follows:
1.
Check the grid voltage. If this is higher than 260
V, the Windy Boy 5000 / 6000 will not be fully
operational. In this case, contact the local grid
operator for assistance.
Max. 260V!
The maximum grid voltage for feeding
electricity into the grid is 260 V!
2.
Isolate the grid connection (switch the line circuit
breaker to its "off" position), make sure it cannot
be switched back on, and test to make sure no
voltage is present.
You must make sure that no voltage is
present at the AC output before opening
the Windy Boy!
3.
Remove the screws that secure the case of the
Windy Boy 5000 / 6000 and remove the cover.
4.
Connect the earth wire (PE) of the mains cable
to the left terminal of the right terminal block
(see the figure on the right).
PE conductor connection
1.
2.
3.
Off!
Netzw
echselr
ichter fü
r Wind
energie
anlage
n
Grid tie
d inver
ter for w
ind turb
ines
Pac
903W
Upv
330V
Windy
Boy
N
L1
230 Vac: