Cable losses of the windy boy 5000 – SMA WB 5000 Installation User Manual
Page 21
SMA
Technology AG
Installation requirements
Installation Guide
WB50_60-11:SE4005
Page 21
The mains grid impedance at the AC input of the Sunny Boy 3800 must be less than
1 Ohm or the protective equipment may not work properly. In addition, we
recommend dimensioning the conductor cross-section so that line losses do not
exceed 1% at the nominal power. Line losses depending on the cable length and
cross-section are shown in the graph below. Multi-wire cables with copper forward
and return conductors are used.
Cable losses of the Windy Boy 5000
The maximum cable lengths for the different cable cross-sections are as follows:
Conductor cross-section
4.0 mm²
6.0 mm²
10.0 m²
16 mm²
Max. length
12 m
18 m
31 m
49 m