SMA WB 5000 Installation User Manual
Page 23
SMA
Technology AG
Installation requirements
Installation Guide
WB50_60-11:SE4005
Page 23
The Windy Boy 5000 / 6000 is designed for operation on 230 V grids and works at
grid voltages from 198 V to 260 V and frequencies from 49.8 Hz to 50.2 Hz, or from
59.8 to 60.2 Hz.
AC output limit values, at 50 Hz
AC output limit values, at 60 Hz
The Windy Boy 5000 / 6000 is fitted with an automatic grid frequency identifier.
Therefore, it can be connected to a 50 or 60 Hz system without further
parameterization. Always follow the grid operator's instructions.
AC output limit values, at 50 Hz
Voltage range
198 V ... 260 V
Frequency range
49.8 Hz ... 50.2 Hz
Voltage range programmable
between
180 V ... 265 V
Frequency range programmable
between
45.5 Hz ... 54.5 Hz
AC output limit values, at 60 Hz
Voltage range
198 V ... 260 V
Frequency range
59.8 Hz ... 60.2 Hz
Voltage range programmable
between
180 V ... 265 V
Frequency range programmable
between
55.5 Hz ... 64.5 Hz