beautypg.com

SMA WB 5000 Installation User Manual

Page 23

background image

SMA

Technology AG

Installation requirements

Installation Guide

WB50_60-11:SE4005

Page 23

The Windy Boy 5000 / 6000 is designed for operation on 230 V grids and works at
grid voltages from 198 V to 260 V and frequencies from 49.8 Hz to 50.2 Hz, or from
59.8 to 60.2 Hz.

AC output limit values, at 50 Hz

AC output limit values, at 60 Hz

The Windy Boy 5000 / 6000 is fitted with an automatic grid frequency identifier.
Therefore, it can be connected to a 50 or 60 Hz system without further
parameterization. Always follow the grid operator's instructions.

AC output limit values, at 50 Hz

Voltage range

198 V ... 260 V

Frequency range

49.8 Hz ... 50.2 Hz

Voltage range programmable
between

180 V ... 265 V

Frequency range programmable
between

45.5 Hz ... 54.5 Hz

AC output limit values, at 60 Hz

Voltage range

198 V ... 260 V

Frequency range

59.8 Hz ... 60.2 Hz

Voltage range programmable
between

180 V ... 265 V

Frequency range programmable
between

55.5 Hz ... 64.5 Hz

This manual is related to the following products: