Technical Data

Installation Guide

SCxxxHE-IEN104432

99

Power consumption

* Internal consumption measured in clock-rate operation with activated AC fans, activated DC fans and power unit cooling unit at

100 % Minimum connected load per phase < 1 500 W

Sunny Central Control interfaces

*Terminal for an analog sensor provided by the customer in two-wire and four-wire version

Protection rating and environmental conditions

Internal consumption in operation*

P

day

< 1 500 W

Internal consumption in night mode

P

night

< 100 W

Internal power supply / grid structure

3 x 230 V, 50 / 60 Hz, TN-S grid /
TNC grid / TT grid

External pre-fuse for internal power supply

B 20 A, 3 pol.

Communication (NET Piggy-Back, optional)

Analog, ISDN, Ethernet

Analog inputs*

1 x PT 100, 5 x A

in

Overvoltage protection for analog inputs

Optional

Sunny String-Monitor connection (COM1)

RS485

PC connection (COM2)

RS232

Potential-free contact (ext. malfunction report)

1

Protection rating as per EN 60529

IP20

Protection rating as per EN 60721-3-3
Environmental conditions:
fixed location, with protection against wind and
weather

Classification of

• chemically active substances:

3C1L

• mechanically active

substances: 3S2

Permissible ambient temperatures

T

‒20 °C … +50 °C

Relative humidity, not condensing

U

air

15 % … 95 %

Max. altitude above sea level

Mean sea
level

1 000 m

Fresh air consumption

V

air

6 200 m³/h