SMA SC 100 Indoor Installation User Manual
Page 47

SMA Solar Technology AG
Appendix B
Installation Guide
SC-100-IEN093231
47
Please note:
• the “Sunny Central Transport Instructions”,
• the “Sunny Central Installation Guide”,
• when installing the SC 100 Outdoor, a suitable foundation, sufficient ventilation and
appropriate sun shading systems are necessary
Standards
EMC
EN 61000-6-2,
EN 61000-6-4
Grid monitoring
per VDEW regulations
CE conformity
yes
Protection rating and ambient conditions
Protection rating per EN 60529
IP21
Permissible ambient temperature
T
-20 °C ... +50 °C
c)
Relative humidity, not condensing
U
air
15 ... 95 %
Max. altitude (above sea level)
1,000 m
Air quality (minimum requirements) per
EN 60721-3-3
fixed location, with protection against wind
and weather.
• Classification of
chemically active
substances: 3C1L
• Classification of
mechanically active
substances: 3S2
Fresh air consumption
V
air
2,300 m³/h
Air duct for outdoor installation
drawn through roof
blown out through roof
a)
Specifications apply to irradiation values = 1000
b)
Terminal for an analog sensor provided by the customer in two-wire systems
c)
Compliance with nominal values up to an ambient temperature of +40 °C, with an ambient
temparature of +50 °C maintanance of the nominal values up to two houres
Sunny Central data
Symbol
SC 100 indoor
Jahr
kWp
kWh
⋅