11 Rating for a line circuit breaker

Required technical information for the inverters used

Maximum output current = 5 A

Maximum permissible fuse protection for the inverter = 16 A

The choice of cable together with the way it is routed, ambient temperatures and other
underlying conditions limit the maximum fuse protection for the cable.

In our example we assume that the chosen cable (2.5 mm²) is ideally routed and
can take a nominal current of 11 A.

Selecting a line circuit breaker:

The maximum possible nominal current for the cable used and the maximum
possible fuse protection for the inverter now limit the maximum possible nominal
current for the line circuit breaker.

In our example, 10 A is possible.

However, the thermal suitability of the line circuit breaker still needs to be checked.

Example for the thermal rating for a line circuit breaker in a photovoltaic electrical
power unit operated in parallel with the low-voltage grid.
We assume a PV system with 9 Sunny Boy SB 1100LV inverters, with three
inverters per phase.