Installation requirements

Installation Guide

SB1100LV-11:SE2006

Page 17

AC cable system impedance should not exceed 1 ohm. This is necessary, amongst other
things, for the correct operation of impedance observation. In addition, we recommend
dimensioning the conductor cross-section so that line losses do not exceed 1% at the
nominal power. Line losses depending on the cable length and cross-section are shown
in the graph below. Multi-wire cables with copper forward and return conductors are
used.

The maximum cable lengths for the different cable cross-sections are as follows:

Conductor cross-section

1.5 mm²

2.5 mm²

Max. length

21 m

35 m

Do not use cables where the losses will exceed 1.0%

Cable length

Line l

o

ss

es