8.4.2 Parameter settings for Germany

Grayed out parameters are only displayed in installer mode. The table below contains
the parameters that are applicable in Germany.

Name

Unit

Value range

Factory setting

ACVtgRPro

V

230 ... 300

253

AntiIsland-Ampl * grd

0 ... 10

0

AntiIsland-Freq * mHz

0 ... 2000

500

Default *

GER/VDE0126-
1-1, GB/G83,
SP/RD1663,
Off_Grid,
Other, trimmed

GER/VDE0126-1-1

dFac-Max *

Hz/s

0.1 ... 4.0

0.25

dZac-Max *

mOhm

0 ... 20000

750

E_Total

kWh

0 ... 200000

Fac-delta- *

Hz

0.1 ... 4.5

2.45

Fac-delta+ *

Hz

0.1 ... 4.5

0.19

h_Total

h

0 ... 200000

I-NiTest *

mA

0 ... 7500

6000

Operating mode

MPP, UKonst,
Stopp, Turbine
Mode, Off Grid

MPP

Storage function

Default
Parameter, Reset
Operating Data,
Reset Fault

None

Speicher/
Storage

Permanent,
volatile

Permanent

T-Start *

s

5 ... 300

10

T-Stop

s

1 ... 3600

2

Uac-Min *

V

160 ... 230

198

Uac-Max *

V

230 ... 300

260

Upv-Start

V

20 ... 60

25

Usoll-Konst

V

26 ... 63

63