beautypg.com

3 country-specific parameter settings, Country-specific parameter settings – SMA SB 1100LV User Manual

Page 42

background image

Technical data

SMA

Technologie AG

Page 42

SB1100LV-11:SE2006

Installation Guide

8.4.3 Country-specific parameter settings

The parameters listed below represent country-specific settings and are only displayed
in installer mode. All other parameters are international and can be viewed in the table
in chapter 8.4.2.

Parameters designated with * are safety-related grid monitoring parameters. To
change the SMA grid guard parameters, you must enter you personal SMA grid
guard password (Inst.-Code). Please call the Sunny Boy Hotline to obtain your
personal SMA grid guard password.

Name

Unit

Country settings

Germany

Great Britain

Spain

Default

GER/
VDE0126-1-1

GB/G83

SP/RD1663

dFac-Max

Hz/s

0.25

0.2

2

dZac-Max

mOhm

750

350

350

Fac-delta-

Hz

2.45

0.5

0.98

Fac-delta+

Hz

0.19

0.5

0.98

I-Ni-Test

mA

6000

0

0

T-Start

s

10

180

10

Uac-Min

V

198

209

199

Uac-Max

V

260

261

250