5.8.2 Connecting a generator (optional)

1. Select a suitable opening for the cable of the generator and poke a hole through it with a pointy

tool.
The cable has to be tightly enclosed by the opening after it is inserted.

2. Pull the cable of the generator through the opening into the Automatic Switch Box.
3. Connect PE to the "X6/Generator" connection terminal according to the label.
4. Connect N to the "X6/Generator" connection terminal according to the label.
5. Connect L1, L2, and L3 to the fuse element "F6 generator" according to the label. Torque:

4 Nm +/– 20 %

☑ The generator is now connected.