5.8 Generator connection (optional)

Cable requirements

The cable type and laying method must be suitable for the application and use location.

5.8.1 Sizing the lead fuse

ATTENTION!
Cable overload due to incorrect design. Destruction of the cable.

• Select the required cable cross section according to the nominal power of the

generator.

• The design of the output fuse of the generator may affect the design of the cable to

the PV system.

• If the generator does not have an output fuse, implement the cable connection to the

Automatic Switch Box in a ground-fault proof and short-circuit proof manner. As an
alternative - especially for long cable distances - you can install an additional fuse
box close to the generator.

Object

Description

Value

A

Cable cross-section

Max. 16 mm

2

B

Strip insulation

18 - 20 mm

Wire sleeves
When using fine-strand cables, also use wire sleeves.
This only applies for the cable connected to the "F6 Generator" fuse element.

Sizing the lead fuse
Size the lead fuse in accordance with the requirements of the generator. You can use a
lead fuse of 40 A at the most. Use type D02 lead fuses.
D02 fuse plugs with a nominal current of 35 A are included in the scope of delivery.
However, you must verify that they meet the requirements.