10  Troubleshooting

Installation Manual

PVO-BOX-IA-en-10

45

10 Troubleshooting

10.1 LED Displays

The LEDs for fault indication are 2-colour. They glow red if operation is currently interrupted. They
glow yellow if a fault has previously occurred, but normal operation is currently possible.
The possible combinations are given in the following table. The "x" entry in the table means that the
previous display of the LED is retained.

Description and corrective measure

Flashing
green

x

x

x

x

Ready for operation

Green

x

x

x

x

Operation

x

Yellow,
red

x

x

x

FE connection fault or AC connection fault:

– L / N swapped
– N not connected (SMA PV Offset Box

connected between L1 and L2)

– FE connection interrupted
– Voltage difference between connected

N conductor and FE larger than 50 V
(AC or DC)

• Check AC-side installation.

x

x

Yellow,
red

x

x

DC connection fault:

– DC connections reverse poled
– DC connection to PV array interrupted
– Installed in an area with insufficient

irradiation, or irradiation interrupted
during the day

– SMA PV Offset Box is disconnected on

the AC or DC side during the day.

– Regeneration time too short (average

night period is less than 5 hours)

• Check DC-side installation.