beautypg.com

Cooling, Esd prevention, Table 2 – H3C Technologies H3C WX5500E Series Access Controllers User Manual

Page 9

background image

3

Table 2 Dust concentration limit in the equipment room

Substance

Concentration limit (particles/m

3

)

Dust particles

≤ 3 x 10

4

(No visible dust on desk in three days)

NOTE:

Dust particle diameter ≥ 5 μm

To eliminate corrosion and premature aging of components, the equipment room must also meet limits on

salts, acids, and sulfides, as shown in

Table 3

.

Table 3 Harmful gas limits in an equipment room

Gas Max.

(mg/m

3

)

SO

2

0.2

H

2

S 0.006

NH

3

0.05

Cl

2

0.01

Cooling

The device uses left to right airflow for heat dissipation. Plan the installation site for adequate ventilation.

H3C recommends that you leave a minimum of 10 cm (3.94 in) of clearance around the air vents.

Make sure the rack is well ventilated.

Figure 1 Airflow through the device chassis

ESD prevention

To prevent electrostatic discharge (ESD), follow these guidelines:

Ground the device properly.

Take dust-proof measures for the equipment room. For more information, see "

Cleanness

."

Maintain the humidity and temperature at a proper level. For more information, see "

Temperature

and humidity

."

This manual is related to the following products: