Cooling, Esd prevention, Table 2 – H3C Technologies H3C WX5500E Series Access Controllers User Manual
Page 9
3
Table 2 Dust concentration limit in the equipment room
Substance
Concentration limit (particles/m
3
)
Dust particles
≤ 3 x 10
4
(No visible dust on desk in three days)
NOTE:
Dust particle diameter ≥ 5 μm
To eliminate corrosion and premature aging of components, the equipment room must also meet limits on
salts, acids, and sulfides, as shown in
.
Table 3 Harmful gas limits in an equipment room
Gas Max.
(mg/m
3
)
SO
2
0.2
H
2
S 0.006
NH
3
0.05
Cl
2
0.01
Cooling
The device uses left to right airflow for heat dissipation. Plan the installation site for adequate ventilation.
•
H3C recommends that you leave a minimum of 10 cm (3.94 in) of clearance around the air vents.
•
Make sure the rack is well ventilated.
Figure 1 Airflow through the device chassis
ESD prevention
To prevent electrostatic discharge (ESD), follow these guidelines:
•
Ground the device properly.
•
Take dust-proof measures for the equipment room. For more information, see "
."
•
Maintain the humidity and temperature at a proper level. For more information, see "