Figure 21 acoa load points – AEC ACOA Series Air-Cooled Central Chillers User Manual
Page 51
Symptom
Possible cause
Solution
Compressor cycles on low
pressure control.
Improper water flow.
Check pressure drop across
evaporator for proper flow.
Fouled evaporator.
Backflush and/or clean.
Compressor cycles off on
high pressure control.
Compressor discharge valve
partially closed.
Open valve fully and close with
one turn.
Air in system.
Purge condenser coils.
Overcharge of refrigerant.
Reclaim system while in
operation until bubbles show in
sight glass. Close valve and
add small amount of
refrigerant until sight glass just
clears.
High pressure control
improperly set.
Adjust the control.
Condenser fan inoperative.
Check, replace or repair set
screw (pulley), fan motor, or
inoperative fan control.
Dirty condenser.
Clean condenser surfaces with
brush and/or vacuum.
Fan cycle switches
inoperative or set too high.
Check and readjust.
Fan motors not running.
Check contactor, check motor,
check capacitor (if single
phase).
Fan motor reverse rotation.
Reverse two fan motor leads
(three-phase only).
Figure 21
ACOA Load Points
ACOA
Isolator weights
Oper.
model
Dimensions (inches)
Load by position (lbs.)
weight
number
A
B
C
D
E
#1
#2
#3
#4
#5
#6
#7
#8
lbs.
ACOA15
19.0”
83.0” 37.3 543
378
572
372
1,865
ACOA20
19.0”
83.0” 37.3 595
421
606
395
2,107
ACOA25
19.0”
83.0” 37.3 651
471
653
433
2,208
ACOA30
19.0” 69.0”
119.0” 37.3 597
487
298
608
476
281
2,747
ACOA35
19.0” 69.0”
119.0” 37.3 640
525
309
638
498
285
2,895
ACOA45
19.0”
83.0” 80.3” 1,025
867
1,140
997
4,029
ACOA55
19.0” 69.0”
119.0” 80.3” 974
780
341
1,045
1,047
554
4,741
ACOA70
19.7” 69.0”
119.0” 80.3” 1,024
952
593
1,112
1,103
608
5,392
ACOA80
12.0” 92.0”
172.0” 83.0” 1,340
1,514
715
1,340
1,514
715
7,138
ACOA90
12.0” 92.0” 172.0” 252.0” 83.0” 1,242
1,562
480
308
1,295
1,868
1,064
618
8,437
ACOA100 12.0” 92.0” 172.0” 252.0” 83.0” 1,289
1,647
516
309
1,348
1,972
1,106
620
8,807
ACOA110 12.0” 92.0” 172.0” 252.0” 83.0” 1,234
1,814
974
438
1,268
1,855
1,313
751
9,647
ACOA125 12.0” 92.0” 172.0” 252.0” 83.0” 1,273
1,844
1,330
758
1,273
1,844
1,330
758
10,410
ACOA135 12.0” 92.0” 172.0” 252.0” 83.0” 1,321
2,032
1,539
844
1,321
2,032
1,539
844
11,472
Page 50
ACOA Series Air-Cooled Central Chillers