Step 1, Caution – AEC ACOA Series Air-Cooled Central Chillers User Manual
Page 29
Step 1
4. Opstat
4TAS-1
opens as water temperature reaches minimum set point. Liquid line
solenoid
1SOL
de-energizes and Circuit 1 refrigerant flow stops. Relay
8CR
de-
energizes, removing
4PS-1
bypass (
4PS-1
now controls pumpdown). Compressor 1
remains running and Circuit 1 pumpdown begins.
5. When suction pressure drops to the pumpdown limit,
4PS-1
opens and Compressor 1
stops. Circuit 1 pumpdown and unload sequence is now complete, and all Circuit 1
controls are back to standby status.
Figure 11
ACOA Control Settings and Set Points (Unit is Off)
ACOA Control Settings
Time
Delay
1TR-1 & 2
5 Min.
3PS-1 & 2
120 Sec.
9PS-1 & 2
120 Sec.
4TR-2
10 Sec.
5TR-1 & 2
2 Min.
Pressure (PSIG)
Open
Close
1PS-1 & 2
360
10, 11PS-1
140
190
10, 11PS-2
160
21-0
10, 11PS-3
170
230
Temperature
Open
Close
4TAS-1
LWT + .40R
LWT + .55R
4TAS-2
LWT + .55R
LWT + .70R
4TAS-3
LWT + .70R
LWT + .85R
4TAS-4
LWT + .85R
LWT + R
3TAS
40ºF
43ºF
ACOA Set Points
Percentage
of ethylene
Minimum
ambient
Minimum
9PS open
4PS
open
4PS
close
Minimum
2TAS open
glycol
ºF
ºC
psig
kPa
psig
kPa
psig
kPa
ºF
ºC
0%
32ºF
0ºC 55 psig 379 kPa 45 psig 310 kPa 70 psig 483 kPa 38ºF
3ºC
10%
27ºF -3ºC 49 psig 338 kPa 39 psig 269 kPa 64 psig 441 kPa 33ºF
1ºC
20%
18ºF -8ºC 39 psig 269 kPa 29 psig 200 kPa 54 psig 372 kPa 24ºF
-4ºC
30%
3ºF -16ºC 33 psig 228 kPa 23 psig 159 kPa 48 psig 331 kPa
9ºF -13ºC
40%
-13ºF -25ºC 33 psig 228 kPa 23 psig 159 kPa 48 psig 331 kPa -7ºF -22ºC
50%
-20ºF -29ºC 33 psig 228 kPa 23 psig 159 kPa 48 psig 331 kPa -14ºF -26ºC
Caution!
Do not set 9PS, 4PS, or 2TAS lower than indicated for your glycol concentration—
the AEC, Inc. warranty is voided! The AEC, Inc. warranty does not cover freeze-up!
Figure 12
Page 28
ACOA Series Air-Cooled Central Chillers