Run cycle sequence (increasing load), Step 1, Step 2 – AEC ACOA Series Air-Cooled Central Chillers User Manual
Page 27: Step 3
2. Run Cycle Sequence (Increasing Load)
• Customer contacts close
Step 1
1. Opstat
4TAS-1
closes as return chilled water temperature starts to rise. Relay
8CR
bypasses pumpdown switch
4PS-1
to remove it from the control circuit.
Note: Go to Step 4 if Compressor 1 is off for more than five (5) minutes.
2. Cycle timer
1TR
times out and closes (up to a five (5) minute delay).
3. Compressor 1 starts. Contactor auxiliary switch energizes liquid line solenoid
1SOL
and
Circuit 1 refrigerant flow starts. Compressor 1 unload solenoid
3SOL
energizes through
4TAS-NC2
and
NC4
. Compressor 1
unloads one bank of cylinders.
4. Oil failure switch
3PS-1
starts to time open (120 sec. delay). Low pressure switch
9PS-1
starts to time open (120 to 240 sec. delay).
Note: If oil pressure or suction pressure is not established at a normal level within the above-
listed delay times, Circuit 1 shuts down.
5. Circuit 1 oil and suction pressure rise to normal levels, and
3PS-1
and
9PS-1
terminate
the time open sequence.
First stage capacity is now on line.
Step 2
6. Opstat
4TAS-2
closes as water temperature continues to rise. Compressor 1 unload
solenoid
1SOL
de-energizes as
4TAS-NC2
opens. Compressor 1 loads up to 100%.
Second stage capacity is now on line.
Step 3
7. Opstat
4TAS-3
closes as water temperature continues to rise. Relay
9CR
bypasses
pumpdown switch
4PS-2
to remove it from the control circuit. Staging timer
4TR-2
delays Compressor 2 start (10 to 30 seconds).
8. Staging timer
4TR-2
closes. If cycle timer
1TR-2
times out, Compressor 2 starts 100%
loaded. Contactor auxiliary switch energizes liquid line solenoid
2SOL
and circuit 2
refrigerant flow starts. Oil Failure switch
3PS-2
starts to time open (120 sec. delay). Low
pressure switch
9PS-2
starts to time open (120 to 240 sec. delay).
Note: If oil pressure or suction pressure is not established at a normal level within previously-
listed delay times, Circuit 2 shuts down.
Page 26
ACOA Series Air-Cooled Central Chillers