Sequence of Operation

4-1 General Information

The operating thermostat (opstat) labeled

4TAS

monitors return chilled water/air temperature

and activates various steps of capacity control to maintain controlled leaving chilled water
temperature or return air temperature.

Each model has similar control logic. Refer to your wiring diagram located on the inside control
panel door for your control layout for more information.

4-2 Circuit Operation

Typical 2 compressor control sequence of operation 4 step capacity control, continuous
pumpdown. Refer to the typical wiring diagrams.

1. Unit on Standby

• Main field disconnect switch closed

• 115 VAC control power on

S1

control switch on

4TAS-1

through

4TAS-4

opstat contacts open or customer control contacts open

2TAS

freezestat closed

FLS

flow switch closed

CWP

chiller pump auxiliary contacts closed

• Water flow rates nominal

• Compressor control switches closed

• All safety switches closed

• Pumpdown during standby

Any one of the compressors may come on for a short time and pump down if any low side
pressure buildup occurs during the standby period. The

1TR

cycle timer locks out for five (5)

minutes after a pumpdown before the compressor can restart. Pumpdowns can be expected
immediately following a normal

ON

cycle as residual liquid in the low side vaporizes, causing

the

4PS

pumpdown switch to close momentarily.