Data transmission
- analogue input

On change-of-state + after
update period elapsed

Sample time configurable 10 secs -
5 days. Change of state sensitivity
configurable 0.05 to 20mA.
Update time configurable 10 secs -
5 days.

Protocol

Addressed data frame with
16 bit CRC,
synchronous DFSK

Each transmission may be
configured to be sent 1 - 5 times

Inputs

Digital Inputs

2 inputs

Suitable for voltage free contacts or
NPN transistor, input debounce 0.5
second

Pulse Inputs

505U-2 - 2 inputs

Share digital inputs. Max rate
100Hz, min. pulse width 3ms.

Analogue Input

One 0 - 20 mA

(suitable for 4 - 20 mA, 0
- 10mA)

“floating” differential input,
common mode voltage 15V. 10 -
12V DC for powering external
loops provided, 25 mA max.
Resolution 12 bit, Accuracy <
0.1%. Transducer warm-up time
configurable 1 - 255 seconds.

Analogue Input Setpoint

Configurable high & low setpoint
may be transmitted to remote units,
allowing set/reset of remote digital
outputs

System Parameters

Network Configurations

Max. number of 505U
inputs is >20 000 if 105U-
C modules are used as
receivers.

505U is compatible with 105U
radio telemetry units which may be
used as repeaters, provision of
outputs, or as network master unit
to connect to PLC or PC

User Configuration

Configuration Software

Diagnostics

On board diagnostics

Automatic check on
startup

Microprocessor operation OK