Westermo RM-505U-2-E User Manual
Page 43

User Manual
MAN_505_1.7.DOC
Page 43
Data transmission
- analogue input
On change-of-state + after
update period elapsed
Sample time configurable 10 secs -
5 days. Change of state sensitivity
configurable 0.05 to 20mA.
Update time configurable 10 secs -
5 days.
Protocol
Addressed data frame with
16 bit CRC,
synchronous DFSK
Each transmission may be
configured to be sent 1 - 5 times
Inputs
Digital Inputs
2 inputs
Suitable for voltage free contacts or
NPN transistor, input debounce 0.5
second
Pulse Inputs
505U-2 - 2 inputs
Share digital inputs. Max rate
100Hz, min. pulse width 3ms.
Analogue Input
One 0 - 20 mA
(suitable for 4 - 20 mA, 0
- 10mA)
“floating” differential input,
common mode voltage 15V. 10 -
12V DC for powering external
loops provided, 25 mA max.
Resolution 12 bit, Accuracy <
0.1%. Transducer warm-up time
configurable 1 - 255 seconds.
Analogue Input Setpoint
Configurable high & low setpoint
may be transmitted to remote units,
allowing set/reset of remote digital
outputs
System Parameters
Network Configurations
Max. number of 505U
inputs is >20 000 if 105U-
C modules are used as
receivers.
505U is compatible with 105U
radio telemetry units which may be
used as repeaters, provision of
outputs, or as network master unit
to connect to PLC or PC
User Configuration
Configuration Software
Diagnostics
On board diagnostics
Automatic check on
startup
Microprocessor operation OK