Westermo RM-505U-2-E User Manual
Page 17
User Manual
MAN_505_1.7.DOC
Page 17
No. of change messages per year
=
2 (twice per year) * 2 (on to off and off to on)
=
4
No. of “off” update messages per year
=
364 (approximately)
No. of “on” update messages per year
=
2 (twice per year) * 16 (4 hours @ 15 min update)
=
32
Total messages for digital input
=
4 + 364 + 32
=
400
Pulse input
Update time
1 day
Sensitivity 50
Average pulse rate is 1 pulse per hour, with peak rate of 20 per hour, for 10 hours, three times per year.
No. of change messages (normal rate)
=
0 (time for 50 pulses is more than the update time)
No. of change messages (peak rate)
=
3 (three per year) * 200 (20 per hr for 10 hrs) / 50
=
12
No. of update messages per year
=
363 (approx)
Total messages for pulse input
=
12 + 363 =
375
Analogue input
Sample time 1 hour
Warm-up time 5 secs
Sensitivity
3%
Update time 1 day
Average changes of >3% is twice per day
No. of change messages per year
=
2 (twice per day) * 365
=
730
No. of update messages per year
=
0 (always be a change message each 1 day)
Total messages for analogue input
=
730
Total input messages per year
=
400 + 375 + 730
=
1505
Power consumed in transmissions =
0.005 * 1505 * 2 (2 transmissions per message)
=
15 mAHr per year
Power for analogue loop supply (assume average loop current is 12mA)
No. of analogue measurements per year
=
365 days * 24 hours * 1(sample time)
=
8,760
Power for analogue loop supply
=
0.012 (from above table) * 5 (warm-up time) * 8,760
=
526 mAHr per year
Power for pulse input
Average pulse rate is 1 pulse per hour (0.0003Hz), so power required = 0.06 x 0.0003 per day
=
zero