Westermo GDW-11 User Manual
Page 39
![background image](https://www.manualsdir.com/files/809547/content/doc039.png)
39
6615-2203
… GDW-11 485, two wire half duplex
In this application the GDW-11 485 is set to communicate with a number of units with
RS-485 interface. The communication is 2 wire half duplex at 38 400 bit/s.
GDW-11 485
Termination
1
2
3
4
GSM
Network
Configure the GDW-11 485
AT+CPIN=xxxx
If PIN code required
AT&F
Set the unit to factory default
AT&W
Store default settings
S1:4 ON
Select 2-wire RS-485 half duplex
S2:1,2 ON
Termination / Failsafe active
S3:1,3 ON
38.4 kbit/s
To make switch setting active the power must be cycled from OFF to ON.
See also other documents in the category Westermo Equipment:
- TR-36B (88 pages)
- TD-36 (44 pages)
- TR-36 (36 pages)
- TR-36B (20 pages)
- IDW-90 AT (97 pages)
- GD-01 (206 pages)
- GD-01 (20 pages)
- MRI-128-F4G (175 pages)
- MRI-128-F4G (169 pages)
- GDW-11 485 (380 pages)
- Lynx Series (28 pages)
- ODW-720-F1 (24 pages)
- ODW-720-F2 (36 pages)
- ODW-720-F1 (20 pages)
- ODW-730-F2 (36 pages)
- ODW-730-F1 (24 pages)
- DDW-120 (24 pages)
- DDW-226-EX (24 pages)
- DDW-226-EX (24 pages)
- DR-270 (28 pages)
- DR Series (460 pages)
- ED-2x0 (20 pages)
- MRD-3x0 (199 pages)
- FD-80 (24 pages)
- FDV-206-1D-1S (24 pages)
- GD-01 US (24 pages)
- LD-01 (8 pages)
- IDW-90 (44 pages)
- Lynx-x10-F2G (16 pages)
- Lynx-x08-F2G-S2 (20 pages)
- MDI-110-F3x (16 pages)
- MR-2x0 (28 pages)
- ODW-642 (28 pages)
- PII PoE Injector (12 pages)
- Viper Series (977 pages)
- SDI-5xx (12 pages)
- RFI-xx (32 pages)
- SDI-8xx (16 pages)
- RFIR-xxx (24 pages)
- TD-29 (16 pages)
- SDW-5xx (24 pages)
- TD-23 (24 pages)
- TD-29P (16 pages)
- Viper 408 (20 pages)